beautypg.com

Hanna Instruments HI 720 Series User Manual

Page 11

background image

20

21

Setup Item

Description

Valid Values

Default

Analog Output 1
O.13

Analog output 1

0 to f.s.

1999 μS/cm

maximum value

(O_VARMIN1

(O_VARMAX1)

O_VARMAX1 -5% f.s. for
O_VARMAX1, O_VARMIN1
≤ O_HOLD1 ≤ O_VARMAX1)

O.14

Analog output 1

User selected value,

Previous value

hold mode (note 13)

Previous value

O.15

Analog output 1

0 to f.s.

1000 μS/cm

hold mode value

(it must be within the

(O_HOLD1)

O_VARMIN1 to
O_VARMAX1 interval)

Analog Output 2
O.20

Analog output 2

Recorder (temperature), Recorder

mode (notes 1, 17)

Control-setpoint 2
(conductivity/concentration
/temperature)

O.21

Analog output 2

0-20 mA or

4-20 mA

type

4-20 mA

O.22

Analog output 2

-30.0 to 130.0°C

0.0°C

minimum value

(O_VARMIN2

(O_VARMIN2)

O_VARMAX2 -10°C,
O_VARMIN2

≤ O_HOLD2

≤ O_VARMAX2)

O.23

Analog output 2

-30.0 to 130.0°C

100.0°C

maximum value

(O_VARMIN2

(O_VARMAX2)

O_VARMAX2 -10°C,
O_VARMIN2

≤ O_HOLD2

≤ O_VARMAX2)

O.24

Analog output 2

User selected value,

Previous value

hold mode (note 13)

Previous value

O.25

Analog output 2

-30.0 to 130.0°C

25.0°C

hold mode value

(it must be within the

(O_HOLD2)

O_VARMIN2 to
O_VARMAX2 interval)

Setup Item

Description

Valid Values

Default

Other Parameters
C.70

Hold mode end delay 00 to 99 seconds

00 sec

C.80

On/Off control

00:00 to 30:00 min.

00:00 min

action delay (note 26)

OUTPUT
Relays
O.01

Relay 1 mode

Disabled,

Control-

(see notes 16, 17)

Control-setpoint 1,

setpoint 1

Control-setpoint 2,
Simple cleaning,
Hold mode

O.02

Relay 2 mode

Disabled,

Control-

(see notes 16, 17)

Control-setpoint 1,

setpoint 2

Control-setpoint 2,
Simple cleaning,
Hold mode

O.03

Relay 3 mode

Disabled,

Disabled

(see notes 12, 16)

Simple cleaning,
Advanced cleaning,
Hold mode

O.04

Relay 4 mode

Disabled,

Disabled

(see notes 12, 16)

Simple cleaning,
Advanced cleaning,
Hold mode

O.05

Hold digital output

Disabled or

Hold mode

Hold mode

Analog Output 1
O.10

Analog output 1

Recorder or

Recorder

mode (notes 1, 17)

Control-setpoint 1

O.11

Analog output 1

0-20 mA or

4-20 mA

type

4-20 mA

O.12

Analog output 1

0 to f.s.

0 μS/cm

minimum value

(O_VARMIN1

(O_VARMIN1)

O_VARMAX1 -5% f.s. for
O_VARMAX1, O_VARMIN1
≤ O_HOLD1 ≤ O_VARMAX1)