Echelon i.LON 1000 Internet Server User Manual
Page 15
i
.LON 1000 Internet Server Starter Kit
11
e) Next, Hyperterminal will prompt you for the RS-232 (COM1 or COM2)
communication parameters. The
i
.LON 1000 communicates at 9600bps,
using 8 bit data, 1 stop bit, and no parity. No flow control is necessary. Set
the parameters in the hyperterminal communication property dialog
accordingly.
2
Initialize the
i
.LON 1000’s IP address, subnet mask, and default gateway.
a) Press the PC’s Enter key twice. The
i
.LON 1000 console application should
respond with the ILON> prompt.
b) Type show at the ILON> prompt and press the PC’s Enter key. The
i
.LON
1000
should respond with a display of its current settings.
iLON> show
Software Version: 1.00.00
IP Address: 0.0.0.0
Subnet Mask: 0.0.0.0
Host Name: iLON
Gateway: 0.0.0.0
DHCP: off
MAC ID: 00-D0-71-00-00-26
LonTalk Unique IDs: 80:00:00:00:12:60 through 80:00:00:00:12:6F
LonTalk Xcvr ID: TP/FT-10
LonTalk IP Port: 1628
Config Server: 0.0.0.0 (1628)
Authentication: off
SNTP Servers: 0.0.0.0 (123); 0.0.0.0 (123)
SNTP Synchronized: no