Control setup, Setting up the control - general, Before starting – Bonaire LV User Manual
Page 31: Installation, Controls – installation / setup / commissioning

Multi-Appliance Manual Control
Controls – Installation / Setup / Commissioning
Control setup
SETTING UP THE CONTROL - GENERAL
B
EFORE
S
TARTING
Before attempting to use the setup instructions for the controls system, make sure the low voltage
cable is connected and the 240 volt power has been turned on to the heater / cooler.
The Low voltage controls are connected to the unit control box / controller via a 20-metre low
voltage loom.
NOTE: Do not run the low voltage loom in long parallel runs with 240V mains cables.
Keep the low voltage loom 200mm away from any long runs of mains wiring.
Cross over mains wiring at right angles.
Do not use existing access holes in wall cavities where 240V mains wiring exists.
Drill a new access hole 200mm from the existing hole.
I
NSTALLATION
Where the control is using the thermostat for operation (Gas Central Heating and Dual cycle
Refrigerated Air Conditioning), it must be installed approximately 1.5 metres above the floor level
on a room wall which is most commonly used for best average sensing.
Secure the control back panel to the wall using screws and plugs.
Do not locate control near concealed hot or cold water pipes, warm air ducts, radiators, sunlight,
or draughts from hallways, stairways or fireplaces and seal against draughts through wall cavities.
These can all affect the temperature.
Bonaire Control Systems