American Energy Systems Country Flame Little Rascal User Manual
Page 6

6
combustion, such as occurs during start-up, shut down, or incorrect operation of the room heater will
lead to some soot formation which will collect in the exhaust venting system. The exhaust venting
system should be inspected at least once every year to determine if cleaning is necessary.
SPECIFICATIONS
FUEL TYPE:
A.P.F.I. residential fuel: Premium quality fuel only
Heat Content: 8200 BTU/lb. min.
Bulk Density: 40 lb. /cubic ft. min.
Moisture Content: 8% max
Ash Content: 1% max
Size:
¼”
to
5/16”
diameter
1.”
long
max
Fines: 1% max through 1/8
th
screen
HOPPER SIZE: 55pounds Hopper Capacity
FLUE SIZE:
3” or 4”
TYPE:
PL double wall vent with stainless steel inner liner
AIR INLET:
3” diameter (non-combustible) pipe (recommend double walled B-vent for fresh air only)
AUGER TYPE: Tumac 2 ¼ Auger Pellet Feed System
CONTROLS:
Integrated Feed Rate/Blower Speed Controls
ELECTRICAL: 120 Volts, 2.4 Amp, 60 Hz (always install an approved surge protector)
MEASUREMENTS:
UNIT BODY HEIGHT
22 ¾”
HEIGHT
ON
PEDESTAL
32
¾”
HEIGHT
ON
LEGS
31
1/4”
UNIT
WIDTH
26”
UNIT
DEPTH
19
3/4”
SHROUD
HEIGHT
29
7/8”
SHROUD
WIDTH
45
7/8”
CLEARANCES:
SIDES
1”
BACK
2”
TOP TO COMBUSTIBLE
3”
TOP TO CEILING
3”
*Combustible Flooring must be covered with non-combustible material extending 6” (150 mm) from front
of unit and 8” (205 mm) from unit on each side. The floor protection on the sides of the stove only has to
extend to the vertical sidewall(s) if the clearances are less than 8”.