8. For installations that pass through a vertical wall and not through the roof, The Factory recommends an
installation similar to the one shown in FIGURE 3. Dimension A should be a minimum of 16” and
dimension B should be a minimum of 3”. Any outside vent should have a vertical run of at least 5’. At
the same time, ensure that termination of the flue pipe does not occur just under the roof overhang.
Such a termination can cause smoke to seep back through the roof and into the home. For all flue pipe
runs over 5’, there should be a flue support no less than 5’ apart.
FLUE PIPE
CLEAN OUT "T"
EXTERIOR WALL
JET CAP
FIGURE 3: RECOMMENDED EXTERIOR WALL INSTALLATION
All installations MUST include a fresh air combustion pipe at least 3” diameter. Such a pipe can be rigid metal,
or flexible metal pipe. In newer homes, it is strongly recommended that an exterior fresh air combustion vent
be installed to ensure proper amounts of air are provided to the pellet stoves combustion chamber.