beautypg.com

American Energy Systems Country Flame Little Rascal User Manual

Page 26

background image

26

8. For installations that pass through a vertical wall and not through the roof, The Factory recommends an

installation similar to the one shown in FIGURE 3. Dimension A should be a minimum of 16” and
dimension B should be a minimum of 3”. Any outside vent should have a vertical run of at least 5’. At
the same time, ensure that termination of the flue pipe does not occur just under the roof overhang.
Such a termination can cause smoke to seep back through the roof and into the home. For all flue pipe
runs over 5’, there should be a flue support no less than 5’ apart.

FLUE PIPE

CLEAN OUT "T"

EXTERIOR WALL

JET CAP

FIGURE 3: RECOMMENDED EXTERIOR WALL INSTALLATION


All installations MUST include a fresh air combustion pipe at least 3” diameter. Such a pipe can be rigid metal,
or flexible metal pipe. In newer homes, it is strongly recommended that an exterior fresh air combustion vent
be installed to ensure proper amounts of air are provided to the pellet stoves combustion chamber.