Table 7 — Minimum Outdoor-Air Operating

Temperature

English

UNIT

09DK

HEAD

PRESSURE

CONTROL

TD

°F

COMPRESSOR CAPACITY (%)*

100

75

50

25

Minimum Outdoor-Air

Temperature ° F

All

Sizes

FCPSs and

Motormaster®

III

30
25
20

-20

-20

-20

-20

054,

064

FCPSst

2 Fans

30
25
20

29
38
47

34
40
47

38
42
46

51

53
56

FCPSst

30

12

19

22

43

074-094

2 Fans

ATfis

25

22

25

29

47

2 Fans

20

31

31

36

51

SI

UNIT

09DK

HEAD

PRESSURE

CONTROL

TD
°C

COMPRESSOR CAPACITY (%)*

100 1 75 1 50 1 25

Minimum Outdoor-Air

Temperature ° C

All

Sizes

FCPSs and

Motormaster

III

16.7
13.9
11.1

-29

-29

-29

-29

054,

064

FCPSst

2 Fans

16.7
13.9
11.1

-2

3
8

1

4
8

3
6
8

11

12
13

074-094

FCPSst

2 Fans

ATSs

2 Fans

167
13 9
11 1

-11

-6

-1

-7
-4

-1

-6
-2

2

6
8

11

LEGEND

ATS — Air Temperature Switch

FCPS — Fan Cyciing Pressure Switch

TD — Temperature Difference = Saturated Condensing

Temperature Entering - Entering-Air Temperature

‘interpolation permitted; compressor capacity per condenser circuit.
tAdditional FCPSs needed for 67/33, 33/33/33, and 33/33/17/17%

capacity split applications

NOTES:

1. Fans on the 09DK054-094 units are controlled by ATSs and FCPSs.

See Table 8 for more details.

2. Minimum outdoor temperatures are determined for indoor and out­

door unit combinations of the same capacity.

Table 8 — Fan Cycling Controls Temperature/

Pressure Settings

English

UNIT

09DK

FCPS

OPENS AT 160

±10 psig

CLOSES AT 260

±15 psig

ATS

OPENS AT 70 ± 3° F

CLOSES AT 80 ± 3° F

054,064

FM 3,4‘

...

074-094

FM 3,4*

FM 5,6t

SI

UNIT

09DK

FCPS

OPENS AT 1103

± 69 kPa

CLOSES AT 1793

± 103 kPa

ATS

OPENS AT 21.1 ± 1.7“C

CLOSES AT 26.7 ± 1.7“ C

054,064

FM 3,4‘

...

074-094

FM 3,4*

FM 5,6t

LEGEND

ATS — Air Temperature Switch
FCPS — Fan Cycle Pressure Switch
FM — Fan Motor
‘Fan motors 3 and 4 are each controlled by a FCPS for 100 and

50/50% capacity split applications For other capacity split options,
the accessory fan control kit must be used and additional FCPSs
are required. See accessory fan control kit installation instructions
for more information.

tFan motors 5 and 6 are each controlled by an ATS.

34