The fan cycling pressure switch controls the fans as fol
lows; Fans 3 and 4 are on above 260 ± 15 psig (1793 ±
103 kPa) and off below 160 ± 10 psig (1103 ± 69 kPa). If
pressure is rising between 160 psig (1103 kPa) and 260 psig
(1793 kPa), fans 3 and 4 are off. If pressure is falling from
260 psig (1793 kPa) to 160 psig (1103 kPa) fans 3 and 4
are on.
The air temperature switch controls the fans as follows;
On the 074-094 condensers, below 70 ± 3F(21.1 ± 1.7 C)
outdoor ambient, fans 5 and 6 are off; above 80 ± 3 F
(26.7 ± 1.7 C) fans 5 and 6 are on. Between 70 F (21.1 C)
and 80 F (26.7 C), whether fans 5 and 6 are on or off de
pends on whether temperature is rising or falling. If the tem
perature is rising from 70 F (21.1 C) to 80 F (26.7 C), fans
5 and 6 are off. If the temperature is falling from 80 F
(26.7 C) to 70 F (21.1 C), fans 5 and 6 are on.
Table 6 — Condenser Coil Refrigerant Circuit Data
UNIT
09DK054
09DK064
COIL
No. of Ckts
2
1
2
2
2
1
2
2
Cap. (% Ckt)
50
66
34
16
50
66
34
16
REFRIGERANT
Min Chg/Ckt
kg
lb
11 0
24 2
14.5
31.8
7.5
16.5
3.6
7.6
165
36 3
21.7
47 7
11 3
24.8
5.2
11.5
Oper Chg/Ckt
kg
lb
129
28 4
17.0
37.4
8.8
19.5
4.1
9.0
194
42 7
25.5
56.2
13.3
29.2
6.1
13.5
Vol/Ckt
cu ft
0.019
0.68
0.025
0.89
0.013
0.46
0 006
0.21
0.029
1.01
0.037
1 32
0.02
0.69
0.009
0.32
STORAGE CAPACITY
R-12
kg
lb
197
43 3
25.9
57.0
13.5
29.6
62
137
29.2
64.3
38 4
84 6
20.0
43.0
9.2
20 3
R-22
kg
lb
18.0
39.6
23 7
52.2
123
27 1
5.7
12.5
26 8
58 9
35.2
77.6
183
40 3
85
18 6
R-500
kg
lb
17.0
37.4
22.3
49 2
11.6
25.6
5.4
11.8
25 1
55.2
33.0
72.7
17.2
37 8
79
175
R-502
kg
lb
18.8
41.5
24 8
54 6
12.9
28.4
6.0
13.1
27 9
61 4
36.7
80.8
19.1
42.0
88
19.4
R-134A
kg
lb
19.7
43.3
25.9
57.0
13.5
29.6
6.2
13.7
29 2
64 3
38 4
84.6
20.0
44.0
92
20.3
UNIT
09DK074
09DK084
09DK094
COIL
No. of Ckts
2
1
2
2
2
1
2
2
2
Cap. (% Ckt)
50
68
32
18
50
67
33
17
50
REFRIGERANT
Min Chg/Ckt
kg
lb
15.9
35 0
21.6
47.6
102
22.5
57
12.5
23.9
52.2
31.8
70.1
15 9
35 0
8.0
17.6
26 2
57 8
Oper Chg/Ckt
kg
lb
18.7
41.2
25.4
56.0
12.0
26.5
67
148
28.1
61.8
37 5
82 5
187
41 2
9.4
20.7
30 8
68 0
Vol/Ckt
cu ft
0.028
0.97
0.037
1 32
0.018
0.62
0.010
0.35
0.041
1.46
0.055
1.95
0 028
0.97
0014
0.49
0 046
1.64
STORAGE CAPACITY
R-12
kg
lb
28 5
62 8
38 7
85.3
18.3
40.3
10.2
22 5
43.3
95.3
57.6
127.0
28.8
63.5
144
31 8
47 5
104 7
R-22
kg
lb
26.1
57 5
35 4
78.0
16.8
36.9
9.3
20 6
39.5
87 0
52.7
116.0
26.3
58.0
132
29 0
43.4
95.7
R-500
kg
lb
24.6
54.2
33.4
73.6
15.8
34.8
88
19.4
37 2
82.0
49 7
109 3
24 8
54 7
124
27 3
40.8
90.0
R-502
kg
lb
27.3
60.4
37.1
81 7
17.5
38.6
9.8
21.5
41.3
91 0
55 1
121.3
27.6
60 7
138
30 3
45.4
100.1
R-134A
kg
lb
28.5
62.8
38.7
85.3
18.3
40.3
10.2
22.5
43 3
95 3
57.7
127 0
28 8
63 5
144
31.8
47 5
104 7
NOTE: Storage capacity calculated for 80% liquid and 20% vapor at 90 F (32.2 C)
33