Fig. 37 — common feeder wiring – Carrier 48MA User Manual

Page 53

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

3.

Where a single feeder is to be used, the cooling power tap may be
sized

according

to

the

Cooling

Minimum

Wire

Amps

shown

in

the Power Wiring Data, Table 1 0, provided the tap is 10 ft or less
in length and enclosed in a raceway

Similarly, the heating power tap may be sized according to the

Heating Minimum Wire Amps shown in the table provided the

tap is 25 ft or less in length and enclosed in a raceway

If reheat is necessary for humidity control in all or part of the
modules, use caution in sizing common feeder as heating and

cooling can occur simultaneously in each reheat module

For 200/230 volt units, line protection is internal to the unit
For 460/575 volt units, overcurrent protection must be provided

in each power tap per NEC

Fig. 37 — Common Feeder Wiring