PERFORMANCE DATA
Room Design 75 F/50% Rh
COOLING CAPACITIES
48MA/50ME030
TOTAL UNIT CFM
8,000
10,000
A1K
Outdoor Air Cfm
Outdoor Air Cfm
■ cMr
0
1000
2000
2500
0
1000
2000
2500
Db
Wb
TC
SHC
Kw
TC
SHC
Kw
TC
SHC
Kw
TC
SHC
Kw
TC
SHC
Kw
TC
SHC
Kw
TC
SHC
Kw
TC
SHC
Kw
65
298
215
"29 T'
311
229
30 5
317
240
30 9
319
245
31 0
309
238
30 4
322
252
31 2
328
263
31 6
330
267
31 7
70
298
215
29 7
317
223
30 9
326
228
31.5
329
230
31 7
309
238
30 4
327
246
31.5
335
251
32 1
339
253
32.3
65
292
212
30 7
304
231
31 6
309
247
31 9
312
254
32 1
303
235
31 5
315
254
32.3
320
270
32 7
322
277
32 8
70
292
212
30 7
309
225
31 9
318
235
32 5
322
240
32 8
303
235
31 5
320
248
32.6
328
258
33 1
331
263
33 3
73
292
212
30 7
313
222
32 2
324
228
32 9
328
230
33 2
303
235
31 5
323
245
32.8
332
251
33 5
336
253
33 7
75
292
212
30 7
315
219
32 3
328
222
33.2
333
234
33.5
303
235
31 5
325
242
33.0
336
245-
33.7
340
246
34.0
65
285
209
31 8
297
234
32 6
303
255
33 0
305
264
33 2
296
232
32 5
307
256
33.3
314
277
33 8
316
286
33 9
70
285
209
31 8
302
228
33 0
311
243
33 6
314
250
33 8
296
232
32 5
312
251
33 7
319
266
34 2
322
273
34.4
. 95
75
285
209
31.8
306
222
33 4
320
230
34 2
325
234
34 6
296
232
32 5
317
244
34 0
328
253
34 8
332
257
35 1
78
285
209
31 8
311
217
33 6
326
222
34 7
332
223‘
35 1
296
232
32 5
320
240
34 2
333
244
35.1
—
_
80
285
209
31 8
314
215
33 8
330
216
34 9
337
216
35 4
296
232
32 5
322
237
34 4
336
238
35 4
-
-
-
70
279
207
32 8
295
230
34 0
303
250
34 6
307
260
34 9
289
229
33.5
304
253
34 7
312
273
35 ¡2
315
282
35 5
. TOO
75
279
207
32 8
300
224
34 4
312
237
35 3
317
244
35 6
289
229
33 5
304
246
35 0
319
260
35 8
324
267
36 1
78
279
207
32.8
303
220
34.7
318
229
35.7
324
234
36.1
289
229
33.5
312
242
35.3
324
252
36.2
-
-
-
70
273
204
33 7
288
232
34 9
297
258
35 7
300
269
35 9
282
226
34 5
296
255
35 6
305
280
36 3
308
291
36 6
1V 0
75
273
204
33 7
293
226
35.4
304
245
36.3
309
254
36.6
282
226
34.5
301
249
36.0
311
268
36.8
315
276
37.1
110
78
266
201
34 6
289
224
36.6
303
244
37.7
308
254
38 1
276
223
35.4
297
247
37.2
-
-
-
-
115
75
261
199
35 5
279
231
37 1
291
260
38 2
296
274
38 6
270
220
36 3
287
253
37 8
297
282
38 7
302
296
39 1
OUTDOOR
AIR
TEMP
TOTAL UNIT CFM
11,000
12,000
Outdoor Air Cfm
Outdoor Air Cfm
0
1000
2000
2500
0
1000
2000
2500
Db
Wb
TC
SHC
Kw
TC
SHC
Kw
TC
SHC
Kw
TC
SHC
Kw
TC
SHC
K w
TC
SHC
Kw
TC
SHC
Kw
TC
SHC
Kw
85
65
314
248
30 7
326
263
31 5
332
273
31 8
334
278
31 9
317
259
30 9' 330
273
31 7
335
284
32 0
337
289
32 1
70
314
248
30.7
331
257
31.8
339
262
32.3
312
264
32.5
317
259
30.9
334
268
32.0
342
272
32.5
345
274
32.7
65
307
245
31 8
319
265
32 5
324
281
32 9
326
288
33 1
310
256
32 0
322
275
32 8
328
291
33 1
330
298
33 3
90
70
307
245
31 8
323
259
32 9
331
269
33 4
334
274
33 6
310
256
32 0
327
270
33 1
334
280
33 6
337
284
33.8
73
307
245
31 8
326
256
33 1
336
261
33 7
339
264
33 9
310
256
32 0
329
266
33 3
338
272
33 9
342
275
34.1
75
307
245
31.8
328
253
33.2
339
256
33.9
343
257
34.2
310
256
32.0
331
263
33.4
341
267
34.1
345
268
34.3
65
300
242
32 8
311
267
33 9
317
287
34 1
319
297
34 2
303
253
33 C 314
277
33 9
321
298
34 3
323
307
34 4
70
300
242
32 8
315
261
33 9
323
276
34 4
325
283
34 6
303
253
33 0
319
272
34 1
326
287
34 6
328
294
34 8
95
75
300
242
32 8
321
255
34 3
330
263
35 0
334
267
35 2
303
253
33 0
323
265
34 5 333
274
35.1
_
_
—
78
300
242
32 8
323
251
34 5
335
255
35 3
_
_
_
303
253
33 0
326
261
34 7
-
_
—
80
300
242
32.8
325
249
34.6
-
-
-
-
-
303
253
33.0
328
258
34.8
-
-
-
-
-
-
70
293
240
33 8
307
263
34 9
315
283
35 5
318
292
35 7
296
250
34 1
310
274
35 2
318
294
35 7
321
303
35 9
100
75
293
240
33 8
312
257
35 3
322
271
36 0
326
277
36 3
296
250
34 1
315
268
35 5
324
281
36 2
-
-
-
78
293
240
33.8
315
253
35.5
327
263
36.4
-
-
-
296
250
34.1
318
263
35.7
-
-
-
-
-
105
70
286
237
34 8
300
266
35 9
309
290
36 6
311
302
36 8
289
247
35 1
303
276
36 1
311
300
36 8
3T4
312
37 0
75
286
237
34.8
304
259
36.3
313
278
37.0
-
-
289
247
35.1
367
270
36.5
316
289
37.2
-
-
110
78
279
234
35.7
300
257
37.4
-
-
-
-
-
-
282
244
36.0
302
268
37.6
-
-
-
-
-
_
115
75
273
231
36 6
289
264
38 0
300
293
38 9
-
-
-
276
241
36 8
292
275
38 3
-
-
-
-
Kw
— Compressor Motor Power Input
SHC
— Sensible Heat Capacity (1000 Btuh)
TC
— Total Capacity (1000 Btuh)
NOTES: 1. No values are given where unit cannot maintain the assumed room
design relative humidity since the moisture content of the air leaving
the unit is higher than the assumed room moisture content
2 Ratings are gross and do not include fan motor heat deduction
33