background image

HEATING PERFORMANCE

Table 5 — Electric Heater Performance

UNIT

HEAT TO

TOTAL

STEPS OF HEAT

KW/STEP

SOME

COOL RATIO

HEATER KW

PER MODULE

PER MODULE

016

.75 1

53

2

3 3

&

1 1

70

2

4.4

024

1.5 1

106

3

4.4

028

75 1

66

2

3.3

&

1 1

88

2

4.4

030

1.5 1

132

3

4.4

034

.75 1

79

2

3.3

&

1 1

106

2

4.4

040

1 .5 1

158

3

4.4

Table 6 — Gas Heating Capacities (1000 Btuh)

UNIT

48MA

INPUT

BONNET CAPACITY

Total

Each

Zone

Module

Total

Each Zone Module

Stage 1

Full

016

480

60

360

22.5

45

024

480

60

360

22.5

45

028

600

60

450

22.5

45

030

600

60

450

22 5

45

034

720

60

540

22 5

45

040

720

60

540

22 5

45

NOTES:
1 Ratings are approved for altitudes to 2000 feet At altitudes over

2000 ft, ratings are 4% less for each 1000 ft above sea level.

2. At altitudes up to 2000 ft, the following formula may be used to

calculate air temp rise:

.

bonnet capacity

At = ----------------:--------------

1 09 X air quantity

3. At altitudes above 2000 ft, the following formula may be used:

_______________ bonnet capacity_____________

( 24 X specific weight of air x 60) (air quantity)

4. Maximum allowable gas pressure is 14.0 in wg

Minimum allowable gas pressure for full rated
input is 5 0 in wg

5 Unit design is A G A certified