beautypg.com

Miscellaneous – Carrier 48MA User Manual

Page 21

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Again, 2 jumper wires have to be removed from

the back of the remote panel to isolate the
day/night switch.

MORNING START-UP — To conserve energy and
lower total operating costs, the outdoor dampers
may be closed when starting the system in the
morning. During a warm-up period, when the
system is operated for one or two hours before

occupancy, only building return air should be

heated. The extra load of cold outdoor air intro­

duced uses extra heat energy. Ventilation is
unnecessary until space is occupied, so the air

introduced produces unnecessary heat waste.

The same principle holds true on a cooling day,

when outside air transmits heat and moisture to
the evaporator coil. This extra load above the
return air only load is an unnecessary expense.

This can be offset by wiring a heating or

cooling thermostat across the “Short To Close
Dampers” terminals on the zone control board.

The thermostat senses return air temperature and

the outdoor air damper does not open until the

building is at the required temperature.

A time clock can also be used and set as

follows:

1. Occupied cycle: 8 a.m. to 6 p.m. Outdoor air

damper is open and the system is controlled by
individual zone thermostats.

2. Night setback cycle: 6 p.m. to 6 a.m. Individual

zone thermostats are on night setback (NS)
cycle. The outdoor air damper is closed, the
unit is reset down and controlled by NS
thermostat.

3. Warm-up (or cool-down) cycle: 6 a.m. to 8 a.m.

Outside air damper is closed by time clock and
the system is controlled by indoor zone
thermostats.

Using any method, increased economy is

achieved and building requirements are satisfied.

MISCELLANEOUS

Sound and Vibration

— All roof mounted air

conditioning equipment produces sound and vibra­
tion. On light types of roof construction, sound

and vibration may be transmitted directly to the
occupied space. Accordingly, sound attenuation
and vibration isolation are important design con­
siderations on any rooftop application.

Sound attenuation can be accomplished in

many ways depending on the specific design
construction of the building. Roof mounted units
can be located over unoccupied space (i.e. storage
areas, utility rooms, corridors) where slightly
higher sound levels are not objectionable. Supply
and return duct systems can be acoustically lined
to prevent sound transmission into occupied space.
If open plenum return air systems are used, an
acoustical trap or fiberglass-lined chamber can be
used to attenuate the sound. Simple return duct
elbows and tees with 5-ft minimum fiberglass lined
legs and low static pressure drop should be
considered when using open plenum return air
systems. Figure 23 illustrates a procedure for
forming an acoustical trap using the roof curb area
under a 48MA unit.

NOTES:

1 Dimension A is approximately 7 in for optimum performance

2 Acoustical lining is 1-in 1-lb density, neoprene-coated fiberglass
3 Return air grille should be located at least 15 ft from return air opening

Fig. 23 — Acoustical Trap Installation

19

This manual is related to the following products: