This system opens the dampers when the

indoor fans start. To keep them closed, short
across the W-R terminals on the remote control
panel or the “Short To Close Dampers” terminals
during the NS period.

METHOD NO. 3 -- USING ACCESSORY RE­
MOTE PANEL, HEATING AND COOLING

NIGHT SETBACK AND INDOOR FAN CYCLING

This system requires a:

Carrier

remote

control

panel

assembly

48MA900041

Carrier

heating

and

cooling

thermostat

HH07AT074

Carrier subbase HH93AZ070

Night setback relay (Honeywell fan center

R8227A)

Seven-day timer (Honeywell S659A)

The system (Fig. 22) is a proposed heating and

cooling niglrt setback with fan cycling. The
thermostat is a standard Carrier part with no
switches on the subbase. This requires a NS relay
with normally closed contacts so an alternate,
Honeywell R8227A is required.

Because cooling is not locked out, the clock

switches that close at niglit are used to directly
close the outdoor air dampers by connecting across

R and W on the remote panel accessory. Again the

MUR shuts down the unit (including the indoor

fans). When the NS thermostats reach their set­
tings, the NS relay is energized, opening the NC

contacts and de-energizing the MUR.

However, if a “wild” zone exists, it is allowed

to cool on heating NS or vice versa. This may be an
advantage on some applications between zones.

Again when the day/night is switched to

“Day,” the NS is overridden and the unit operates
normally except the dampers remain closed at
night.

SWITCHES SHOWN IN NIGHT POSITION,

V 'T "V

NOTE: 24V WIRING
BETWEEN CONTROLS

NIGHT SETBACK
RELAY

LEGEND

APS

— Air Pressure Switch

FRS

— Filter Media Runout

Switch

MCR

— Master Cooling Relay

MHR

— Master Heating Relay

MUR

— Mastei Unit Relay

TC

— Thermostat, Cooling

TH

— Thermostat, Heating

c=.OR® Terminal (Circuit Board,

Field or Accessory Conn )

_______ Accessory or Field Wiring

________ Factory Wiring

' Circuit Board Run

FILTER

<3F-ri-]-i-g

XI

. . ¿ X I c 3 x 2

TO REMOTE PANEL

MHR .

=*=o4

MUR

I

MUR

I

-0==j=O=I

MCR |_MCRj

I

l

2

j

l

I_

i

O) SHORT TO

HI H2

^ CLOSE DAMPERS

0

ACCESSORY BOARD

ON BASE UNIT

REMOVE JUMPERS
BETWEEN NC ANDR; CANDW

#

Fig. 22 — Night Setback, Method #3

18

This manual is related to the following products: