beautypg.com

Step 2 — make gas piping connections — the – Carrier 48KH User Manual

Page 5

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

#

m

Fig. 5 — Vent Cap Assembly

Step 2 — Make Gas Piping Connections

— The

gas supply pipe enters unit thru access hole provided.
See Fig. 4 for location. The gas connection to unit is

made to the 1/2-in. FPT gas inlet on gas valve. See
Fig. 6 for inlet location.

Install a separate gas supply line that runs directly

from meter to heating section.

Do not use cast-iron

pipe. Check local utility for recommendations con­

cerning existing lines. Choose a supply pipe that is
large enough to keep pressure loss as low as practical.
Never use pipe smaller than the 1 / 2-in. FPT gas inlet
on gas valve.

When installing gas supply line, observe local

codes pertaining to gas pipe installations. Refer to
National Fuel Gas Code ANSI Z223.1-1980 or
NFPA 54-1980 in absence of local building codes.
Adhere to following pertinent recommendations:

1. Avoid low spots in long runs of pipe. Grade all

pipe 1 /4 in. in every 15 ft to prevent traps. Grade
all horizontal runs downward to risers. Use risers
to connect to heating section and to meter.

2. Support all piping with appropriate hangers, etc.

Use a minimum of one hanger in every 6 feet. For
pipe sizes larger than 1/2 in., follow recom­
mendations of national codes.

7
8

9

10

Control Transformer

11 — Pilot Tube

Compressor Contactor

12 — Model 646A-X Gas

Ground Lug

Valve

Dual Run Capacitor

13 — Pressure Tap Pipe Plug

(for compressor and

14 — Gas Valve Outlet

condenser fan motor)

15 — Gas Manifold

Low-Voltage Pigtail

16 — Gas Burner

Leads

17 — Burner Air Shutter

Compressor/Control

18 — Secondary-Air Shield

Compartment Divider

19 — Blower Flousing

Panel

20 — Evaporator Motor Run

Igniter Module

Capacitor

Manual ON/OFF

21 — Blower/Control Com­

Knob

partment Divider

Gas Valve Inlet

Panel

Pipe Plug — LP

22 — Heating Relay

(Propane) unit pres­
sure switch mounts
here

23 — Cooling Relay

Fig. 6 — Model 48KL036 — Side View

(Partial) with Access Door Removed

3. Apply joint compound (pipe dope) sparingly and

only to male threads of joint when making pipe
connections. Use only pipe dope that is resistant
to action of liquefied petroleum gases as speci­
fied by local and/or national codes.

Never use

pipe thread tape.

4. Install a sediment trap in riser leading to the heat­

ing section. See Fig. 7. This drip leg functions as a
trap for dirt and condensate. Install trap where
condensate cannot freeze. Install this sediment
trap by connecting a piping tee to riser leading to
heating section, so that straight-thru section of
tee is vertical. Then, connect capped nipple into
lower end of tee. Extend capped nipple below
level of gas controls.