TROUBLESHOOTING CHART
Table 9 — Cooling Service Analysis Chart
SYMPTOM
PROBABLE CAUSE
REMEDY
Compressor and con
denser fan will not start
Power failure
Fuse blown or circuit breaker
tripped
Call power company
Replace fuse or reset circuit breaker.
Defective thermostat, contactor,
transformer, or control relay
Replace component
Insufficient line voltage
Determine cause and correct
Incorrect or faulty wiring
Check wiring diagram and rewire correctly
Thermostat setting too high
Lower thermostat setting below room temperature
Compressor will not start
but condenser fan runs
Faulty wiring or loose connections
in compressor circuit
Check wiring and repair or replace
Compressor motor burned out,
seized, or internal overload open
Determine cause Replace compressor.
Defective run/start capacitor,
overload, start relay
Determine cause and replace
One leg of 3-phase power dead
Determine cause
Replace fuse or reset circuit breaker
Compressor cycles (other
than normally satisfying
Refrigerant overcharge or
undercharge
Blow refrigerant, evacuate system, and recharge to
nameplate
thermostat)
Defective compressor
Determine cause, replace
Insufficient line voltage
Determine cause and correct
Blocked condenser
Determine cause and correct
Defective run/start capacitor,
overload, or start relay
Determine cause and replace
Defective thermostat
Replace thermostat
Faulty condenser fan motor or
Replace
capacitor
Restriction in refrigerant system
Locate restriction and remove
Compressor operates
continuously
Dirty air filter
Unit undersized for load
Replace filter
Decrease load or increase unit size
Thermostat set too low
Reset thermostat.
Low refrigerant charge
Locate leak, repair, and recharge
Leaking valves in compressor
Replace compressor
Air in system
Blow refrigerant, evacuate system, and recharge
Condenser coil dirty or restricted
Clean coil or remove restriction
Excessive head pressure
Dirty air filter
Replace filter
Dirty condenser coil
Clean coil
Refrigerant overcharged
Purge excess refrigerant.
Áir in system
Blow refrigerant, evacuate system, and recharge
Condenser air restricted or air
short-cycling
Determine cause and correct
Head pressure too low
Low refrigerant charge
Check for leaks, repair, and recharge
Compressor valves leaking
Replace compressor.
Restriction in liquid tube
Remove restriction
Excessive suction pressure
Fligh heat load
Check for source and eliminate
Compressor valves leaking
Replace compressor
Refrigerant overcharged
Purge excess refrigerant.
Suction pressure too low
Dirty air filter
Low refrigerant charge
Replace filter
Check for leaks, repair, and recharge
Metering device or low side
restricted
Remove source of restriction.
Insufficient evaporator airflow
Increase a ir quantity Check filter — replace if necessary
Temperature too low in condi
tioned area
Reset thermostat
Outdoor ambient below 55 F
Install accessory low-ambient kit
Field-installed filter drier
restricted
Replace.
23