TROUBLESHOOTING CHART

Table 9 — Cooling Service Analysis Chart

SYMPTOM

PROBABLE CAUSE

REMEDY

Compressor and con­
denser fan will not start

Power failure

Fuse blown or circuit breaker

tripped

Call power company

Replace fuse or reset circuit breaker.

Defective thermostat, contactor,

transformer, or control relay

Replace component

Insufficient line voltage

Determine cause and correct

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

Thermostat setting too high

Lower thermostat setting below room temperature

Compressor will not start
but condenser fan runs

Faulty wiring or loose connections
in compressor circuit

Check wiring and repair or replace

Compressor motor burned out,
seized, or internal overload open

Determine cause Replace compressor.

Defective run/start capacitor,

overload, start relay

Determine cause and replace

One leg of 3-phase power dead

Determine cause
Replace fuse or reset circuit breaker

Compressor cycles (other

than normally satisfying

Refrigerant overcharge or
undercharge

Blow refrigerant, evacuate system, and recharge to
nameplate

thermostat)

Defective compressor

Determine cause, replace

Insufficient line voltage

Determine cause and correct

Blocked condenser

Determine cause and correct

Defective run/start capacitor,

overload, or start relay

Determine cause and replace

Defective thermostat

Replace thermostat

Faulty condenser fan motor or

Replace

capacitor

Restriction in refrigerant system

Locate restriction and remove

Compressor operates

continuously

Dirty air filter

Unit undersized for load

Replace filter

Decrease load or increase unit size

Thermostat set too low

Reset thermostat.

Low refrigerant charge

Locate leak, repair, and recharge

Leaking valves in compressor

Replace compressor

Air in system

Blow refrigerant, evacuate system, and recharge

Condenser coil dirty or restricted

Clean coil or remove restriction

Excessive head pressure

Dirty air filter

Replace filter

Dirty condenser coil

Clean coil

Refrigerant overcharged

Purge excess refrigerant.

Áir in system

Blow refrigerant, evacuate system, and recharge

Condenser air restricted or air
short-cycling

Determine cause and correct

Head pressure too low

Low refrigerant charge

Check for leaks, repair, and recharge

Compressor valves leaking

Replace compressor.

Restriction in liquid tube

Remove restriction

Excessive suction pressure

Fligh heat load

Check for source and eliminate

Compressor valves leaking

Replace compressor

Refrigerant overcharged

Purge excess refrigerant.

Suction pressure too low

Dirty air filter

Low refrigerant charge

Replace filter

Check for leaks, repair, and recharge

Metering device or low side
restricted

Remove source of restriction.

Insufficient evaporator airflow

Increase a ir quantity Check filter — replace if necessary

Temperature too low in condi­
tioned area

Reset thermostat

Outdoor ambient below 55 F

Install accessory low-ambient kit

Field-installed filter drier
restricted

Replace.