Carrier 5H User Manual
Page 32
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

A
condenser
selection
that
permits
operation
of the system at a low condensing temperature,
results
in
the
lowest
compressor
motor
brake
horsepower
and
consequently,'
the
lowest
operat
ing
cost.
A
condenser
selection
that
is
heavily
loaded
requires
the
compressor
to
operate
at
a
higher
condensing
temperature,
results
in
higher
compressor
motor
brake
horsepower
and
operat
ing cost.
For
a
given
compressor-condenser
combina
tion,
the
selection
of
a
condensing
temperature
may depend on the ratio between power costs and
water costs, on the quantity of water available, on
the
condensing
temperature
required
to
achieve
compressor
capacity,
or
possibly
the
require
ment to remain within the allowable loading on a
given motor size.
Table 25 - Condenser Water Circuiting
WATER CIRCUITING
ARRANGEMENTS
CONDENSER SIZE
CONDENSER
CHARACTERISTICS
NORMAL USE
Double Circuit
5F20, 5F30
High Water Quantity
Low Pressure Drop
4 Passes
5F40, 5F60
Cooling Tower
3 Passes
All 09RH
Single Circuit
5F20, 5F30
Low Water Quantity
High Pressure Drop
8
Passes
5F40, 5F60
City or Well Water
6
Passes
All 09RH
Manufacturer reserves the right to change any product specifications without notice
SECTION
PAGES
DATE
5F,H-1XA
32
10-66
Printed in U.S.A.
S U P E R S E D E S
SECTION
5F,H-1X
PAGES
1-42
DATE
11-63