beautypg.com

Carrier 5H User Manual

Page 31

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Condenser Duty

- The capacity of a given com­

pressor

is

greatest

at

high

saturated

suction

temperatures.

Because

of

this,

the

compressor

normally

requires

the

largest

condenser

at

these

conditions, or for air conditioning duty.

On

refrigeration

or

low

temperature

applica­

tions,

the

same

compressor

displacement

results

in

a

lower

refrigeration

capacity

and,consequently,

less

heat

rejection.

Thus,

the

condenser

size

is

smaller than would normally be required with the
same compressor on air conditioning duty.

Condenser size is also affected by the refrig­

erant

used,

since

compressor

capacities

(and

thus

heat

rejection)

differ

with

Refrigerants

12,

22, 500, and 502.

Pulldown

-

Condensers

for

systems

subject

to

pulldown

periods,

especially

low

temperature

or

multi-stage systems, should be oversized to some
extent beyond the capacity required at the final
balanced

load

condition.

The

condenser

must

adequately handle the load during the first stages
of pulldown, when the system capacity is substan­

tially greater than at the final condition.

There

are

a

few general

rules that

can be

followed

to

determine

the

amount

of

oversizing

that is required. Much depends, of course, on job
conditions and how often pulldown will be required.

If the pulldown load is sizable, such as in most

water

or

brine

cooling

applications,

check

con­

denser performance when it is handling the total
heat rejection at the maximum rated suction tem­
perature (50 F for most compressors). The con­
denser size and water quantity must be adequate
to handle this start-up load without resulting in
excessive head pressure or excessive water pres­

sure drop. As a rough guide, condenser selected
should have a maximum total heat rejection rating
which is equal to or greater than the compressor

heat rejection at the pulldown conditions.

If this pulldown occurs very infrequenctly, then

it may be possible to select the condenser for the

design conditions and on each start-up limit the
compressor

capacity

by

manually

throttling

the

suction gas flow. This can be done by partially

closing the suction valve but this will extend the

time required to reach design conditions.

If the pulldown is of short duration, such as on

a

direct

expansion

coil,

the

suction

temperature

will drop very rapidly and more than likely design

conditions will be reached before the compressor

would cut out on high pressure. No oversizing of
the condenser would be required.

Whenever

possible

the

selected

condenser

should never be of a larger size than the largest

that will match the compressor used and still be
a standard combination. This should be considered
especially

when

the

condensers

are

to

be

used

with the 5 Series open reciprocating compressors.

Fouling Factors

- The 5F and 09RH condenser

capacity

ratings

in

the

5F,09RH-1XR

are

given

for water side fouling factors of 0.0005, 0.0001

and 0.0002. These fouling factors are the resist­
ance to heat flow introduced by scale and other
water impurities.

Condensers

should

not

be

normally

selected

for

less

than

0.0005

fouling

factor,

even

when

high quality water is available. For lower quality
water,

use

the

larger

fouling

factors

from

the

condenser

ratings,

but

temper

the

factor

accord­

ing to the operating conditions.

The

following

items

affect

the

magnitude

of

the fouling factor selected:

1. Percentage of yearly operating time.

2. Frequency of tube cleaning.
3. Condensing temperature.
4. Type of water treatment.

For

instance,

reduce

the

fouling

factor

when

the operating time is less than 4000 hours per
year, when frequent cleaning of tubes takes place,
or when low condensing temperatures exist.

Water Circuiting Arrangements

- The water cir­

cuiting arrangement selected for the 5F and 09RH
condensers

depends

on

the

available

condenser

water

pressure,

temperature,

quantity

and

source.

Refer to Table 25.

Piping

- On the 5F shell and tube and the 09RH

condensers, excluding those with 14- and 18-inch
diameter shells, it is possible to interchange the
condenser

heads.

This,

however,

should

not

be­

come

a

common

practice

but

done

only

when

absolutely

necessary.

When

it

has

to

be

done

extreme caution and care should be taken to not
ruin or dislocate the microbaffling.

The hot gas discharge line from the compres­

sor to the condenser should be as short as pos­
sible to reduce the hot gas pressure drop.

Refer

to

the

Carrier

System

Design

Manual

for

specific

information

and

recommendations

for refrigerant and water piping.

Economics

- The selection of a condenser re­

quires

the

balancing

of

certain

economic

var­

iables, including:

1. First cost of compressor-condenser combina­

tion.

2. Operating costs.
3. Ratio between power costs and water costs.

Where first cost is the most important consid­

eration,

the

best

combination

of

compressor

and

condensers is the one which has the lowest total
equipment cost.

If owning and operating costs are both impor­

tant,

the

combination

must

be

selected

on

the

basis of both considerations.

S U P E R S E D E S
SECTION

5F,H-1X

PAGES

1-42

DATE

11-63

SECTION
PAGE
DATE

5F,H-1XA

31

10-66