Carrier 5H User Manual
Page 31
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Condenser Duty
- The capacity of a given com
pressor
is
greatest
at
high
saturated
suction
temperatures.
Because
of
this,
the
compressor
normally
requires
the
largest
condenser
at
these
conditions, or for air conditioning duty.
On
refrigeration
or
low
temperature
applica
tions,
the
same
compressor
displacement
results
in
a
lower
refrigeration
capacity
and,consequently,
less
heat
rejection.
Thus,
the
condenser
size
is
smaller than would normally be required with the
same compressor on air conditioning duty.
Condenser size is also affected by the refrig
erant
used,
since
compressor
capacities
(and
thus
heat
rejection)
differ
with
Refrigerants
12,
22, 500, and 502.
Pulldown
-
Condensers
for
systems
subject
to
pulldown
periods,
especially
low
temperature
or
multi-stage systems, should be oversized to some
extent beyond the capacity required at the final
balanced
load
condition.
The
condenser
must
adequately handle the load during the first stages
of pulldown, when the system capacity is substan
tially greater than at the final condition.
There
are
a
few general
rules that
can be
followed
to
determine
the
amount
of
oversizing
that is required. Much depends, of course, on job
conditions and how often pulldown will be required.
If the pulldown load is sizable, such as in most
water
or
brine
cooling
applications,
check
con
denser performance when it is handling the total
heat rejection at the maximum rated suction tem
perature (50 F for most compressors). The con
denser size and water quantity must be adequate
to handle this start-up load without resulting in
excessive head pressure or excessive water pres
sure drop. As a rough guide, condenser selected
should have a maximum total heat rejection rating
which is equal to or greater than the compressor
heat rejection at the pulldown conditions.
If this pulldown occurs very infrequenctly, then
it may be possible to select the condenser for the
design conditions and on each start-up limit the
compressor
capacity
by
manually
throttling
the
suction gas flow. This can be done by partially
closing the suction valve but this will extend the
time required to reach design conditions.
If the pulldown is of short duration, such as on
a
direct
expansion
coil,
the
suction
temperature
will drop very rapidly and more than likely design
conditions will be reached before the compressor
would cut out on high pressure. No oversizing of
the condenser would be required.
Whenever
possible
the
selected
condenser
should never be of a larger size than the largest
that will match the compressor used and still be
a standard combination. This should be considered
especially
when
the
condensers
are
to
be
used
with the 5 Series open reciprocating compressors.
Fouling Factors
- The 5F and 09RH condenser
capacity
ratings
in
the
5F,09RH-1XR
are
given
for water side fouling factors of 0.0005, 0.0001
and 0.0002. These fouling factors are the resist
ance to heat flow introduced by scale and other
water impurities.
Condensers
should
not
be
normally
selected
for
less
than
0.0005
fouling
factor,
even
when
high quality water is available. For lower quality
water,
use
the
larger
fouling
factors
from
the
condenser
ratings,
but
temper
the
factor
accord
ing to the operating conditions.
The
following
items
affect
the
magnitude
of
the fouling factor selected:
1. Percentage of yearly operating time.
2. Frequency of tube cleaning.
3. Condensing temperature.
4. Type of water treatment.
For
instance,
reduce
the
fouling
factor
when
the operating time is less than 4000 hours per
year, when frequent cleaning of tubes takes place,
or when low condensing temperatures exist.
Water Circuiting Arrangements
- The water cir
cuiting arrangement selected for the 5F and 09RH
condensers
depends
on
the
available
condenser
water
pressure,
temperature,
quantity
and
source.
Refer to Table 25.
Piping
- On the 5F shell and tube and the 09RH
condensers, excluding those with 14- and 18-inch
diameter shells, it is possible to interchange the
condenser
heads.
This,
however,
should
not
be
come
a
common
practice
but
done
only
when
absolutely
necessary.
When
it
has
to
be
done
extreme caution and care should be taken to not
ruin or dislocate the microbaffling.
The hot gas discharge line from the compres
sor to the condenser should be as short as pos
sible to reduce the hot gas pressure drop.
Refer
to
the
Carrier
System
Design
Manual
for
specific
information
and
recommendations
for refrigerant and water piping.
Economics
- The selection of a condenser re
quires
the
balancing
of
certain
economic
var
iables, including:
1. First cost of compressor-condenser combina
tion.
2. Operating costs.
3. Ratio between power costs and water costs.
Where first cost is the most important consid
eration,
the
best
combination
of
compressor
and
condensers is the one which has the lowest total
equipment cost.
If owning and operating costs are both impor
tant,
the
combination
must
be
selected
on
the
basis of both considerations.
S U P E R S E D E S
SECTION
5F,H-1X
PAGES
1-42
DATE
11-63
SECTION
PAGE
DATE
5F,H-1XA
31
10-66