Refrigerant 12 and 22 booster compressors – Carrier 5H User Manual
Page 21
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

REFRIGERANT 12 AND 22 BOOSTER COMPRESSORS
Booster Application Data
- The following data
supplements single-stage compressor application
data, and adds information pertaining to booster
application only. Refer to single-stage compres
sor data for all other information.
Rating Basis
- All booster ratings are given in
refrigeration effect and are based on;
1. Use of a liquid-suction heat interchanger. (It
is important to note here that all liquid-suction 
interchangers should have a bypass connection 
on the liquid side so that adjustment can be
made in the event that too much superheating
of the suction gas causes excessive heating of 
the compressor. This is especially true in the 
case of Refrigerant 22, which has a higher 
compression exponent than Refrigerant 12.)
2. The liquid refrigerant at Point "A" (Fig. 15)
being at the saturation temperature corre
sponding to the booster discharge pressure. 
This is also often referred to as the "sat
urated intermediate temperature."
This situation obtained when booster discharge 
gas is condensed in a cascade (refrigerant- 
cooled) condenser, or when using an open flash 
type intercooler in a direct staged system.
When subcooling or the liquid takes place in a 
closed type intercoooler then it is not possible 
to bring the liquid temperature all the way 
down to the saturated intermediate tempera
ture because of the temperature difference 
required for heat transfer thru the liquid coil. 
In this case, the compressor rating must be
3.
decreased
for each 10 F, that the liquid
temperature at Point "A" is above the sat
urated intermediate temperature.
Use of only one-half the standard number of 
suction valve springs per cylinder. All 5F,H 
compressors are factory-assembled with the 
standard number of suction valve springs; 
therefore, one-half of the suction valve springs 
per cylinder must be removed in the field for 
booster application.
"R" Factors
- In a multi-stage compression sys
tem, the intermediate or high stage compressor
must have sufficient capacity to handle the low 
stage (booster) compressor load plus the heat 
added to the refrigerant gas by the low stage 
machine during compression. Likewise, if an 
intermediate stage compressor should be used, 
the high stage compressor must have sufficient 
capacity to handle the intermediate stage com
pressor load plus the heat added to the refrigerant 
gas by the intermediate stage machine during 
compression.
To assist in the selection of higher stage
compressors. Tables 18 thru 20 present "R"
factors which depict the approximate required
relationship between stages at various saturated 
temperature conditions.
To determine the required capacity of a higher
stage compressor, multiply, the lower stage com
pressor capacity by the proper "R" factor from
either Table 18, 19 or 20. Any additional loads
handled at the intermediate pressure must be 
added to this figure to arrive at the total higher 
stage load.
Multi-Stage System Pointers
- A staged system
is essentially a combination of two or more simple 
refrigerant cycles. In combining two or more 
simple flow cycles to form a staged system for 
low temperature refrigeration, two basic types 
of combination are common (Fig. 15).
DIRECT STAGING - Involves the use of compres
sors, in series, compressing a single refrigerant.
CASCADE STAGING - Usually employs two or 
more refrigerants of progressively lower boiling 
points. The compressed refrigerant of the low 
stage is condensed in an exchanger (cascade 
condenser) which is cooled by evaporation of 
another lower pressured refrigerant in the next 
higher stage.
S U P E R S E D E S
SECTION
5F,H-1X
PAGES
1-42
DATE
11-63
SECTION
PAGE
DATE
5F,H-1XA
21
10-66
