DSE Model 7000 Series Control & Instrumentation System Operators Manual

Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 5 15/10/2009 ADM

99

8.12.2 ADJUSTABLE PARAMETERS

Front Panel Configuration Editor

= Only available on DSE7220 / DSE7320 AMF Modules

Section

Parameter as shown on display

Factory Settings

DISPLAY

Contrast

53%

Language

English

LCD Page Timer

5m

Auto Scroll Delay

2s

Current Date and time

hh:mm

EDITOR

Alt Config

Default Config

ENGINE

Oil Pressure Low Shutdown

1.03bar

Oil Pressure Low Pre Alarm

1.17bar

Coolant Temperature Low Warning

70ºC

Coolant Temperature High Pre Alarm

90ºC

Coolant Temperature High Shutdown

95ºC

Remote Start Delay Off Load

5s

Remote Start Delay On Load

5s

Mains Fail Start Delay

5s

Telemetry Start Delay

5s

Start Delay Timer

5s

Pre Heat Timer

0s

Crank Duration Timer

10s

Crank Rest Timer

10s

Safety On Delay

10s

Smoke Limiting

0s

Smoke Limiting Off

0s

Warm Up Timer

0s

Cool Down Timer

1m

Engine Under Speed Shutdown

Inactive

Engine Under Speed Shutdown

1200RPM

Engine Under Speed Warning

Inactive

Engine Under Speed Warning

1350RPM

Engine Over Speed Warning

Inactive

Engine Over Speed Warning

1650RPM

Engine Over Speed Shutdown

1710RPM

Engine Speed Overshoot Delay

2s

Engine Speed Overshoot

0s

Fail To Stop Delay

30s

Battery Under Voltage Warning

Active

Battery Under voltage Warning Delay

1m

Battery Under Voltage

10V

Battery Over Voltage Warning

Active

Battery Over Voltage Warning Delay

1m

Battery Over Voltage Warning

30V

Charge Alternator Failure Warning

Active

Charge Alternator Failure Warning

6V

Charge Alternator Warning Delay

5s

Charge Alternator Failure Shutdown

Active

Charge Alternator Failure Shutdown

4.0V

Charge Alternator Shutdown Delay

5s

Droop control

Inactive

Droop control

4%
(Compatible engine ECUs only)

Fuel Usage Alarm (Running Rate)

0%-100%

Fuel Usage Alarm (Stopped Rate)

0%-100%

GENERATOR

Generator Under Voltage Shutdown

184V

Generator Under Voltage Pre Alarm

196V

Generator Voltage Nominal

230V

Generator Over Voltage Pre Alarm

265V

Generator Over Voltage Shutdown

277V

Generator Under Frequency Shutdown

40Hz

Generator Under Frequency Pre Alarm

42Hz

Generator Frequency Nominal

50Hz

Generator Over Frequency Pre Alarm

55Hz

Generator Over Frequency Shutdown

57Hz

Full Load Rating

500A

Kw Overload Trip

100%

Delayed Over Current

Active

Delayed Over Current

100%

AC System

3 Phase, 4 Wire

CT Primary

600A

CT Secondary

5A

Earth CT Primary

500A

Earth Fault Trip

Inactive

Earth Fault Trip

10%

Generator transient delay

0s