DSE Model 7000 Series Control and Instrumentation System Operators Manual
10
Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 5 15/10/2009 ADM
3.6 GENERATOR CURRENT SENSING
Measurement type
True RMS conversion
Sample Rate
5KHz or better
Harmonics
Up to 10
th
or better
Nominal CT secondary rating
1A or 5A (5A recommended)
Maximum continuous current
5A
Overload Measurement
3 x Nominal Range setting
Absolute maximum overload
50A for 1 second
Burden
0.5VA (0.02
Ω
current shunts)
common mode offset
±2V peak plant ground to CT common terminal
Resolution
0.5% of 5A
Accuracy
±1% of Nominal (1A or 5A) (excluding CT error)
3.7 INPUTS
3.7.1 DIGITAL INPUTS
Number
DSE7200
6
DSE7300
8
Arrangement
Contact between terminal and ground
Low level threshold
2.1V minimum
High level threshold
6.6V maximum
Maximum input voltage
+50V DC with respect to plant supply negative
Minimum input voltage
-24V DC with respect to plant supply negative
Contact wetting current
7mA typical
Open circuit voltage
12V typical
3.7.2 ANALOGUE INPUTS
Oil Pressure
Measurement type
Resistance measurement by measuring voltage across sensor with a fixed current
applied
Arrangement
Differential resistance measurement input
Measurement current
15mA
Full scale
240
Ω
Over range / fail
270
Ω
Resolution
1-2 PSI / 0.1 Bar
Accuracy
±2% of full scale resistance (±4.8
Ω
) excluding transducer error
Max common mode voltage
±2V
Display range
0-200 PSI / 13.7 bar subject to limits of the sensor
Coolant Temperature
Measurement type
Resistance measurement by measuring voltage across sensor with a fixed current
applied
Arrangement
Differential resistance measurement input
Measurement current
10mA
Full scale
480
Ω
Over range / fail
540
Ω
Resolution
1
°
C, 2°F
Accuracy
+/-2% of full scale resistance (±9.6
Ω
) excluding transducer error
Max common mode voltage
±2V
Display range
0
°
C -140
°
C, 32°F - 284°F Depending on sensor