3 terminal specification, 4 power supply requirements, 5 generator and mains voltage / frequency sensing – Winco DSE7300 Series User Manual
Page 9
![background image](/manuals/716100/9/background.png)
DSE Model 7000 Series Control & Instrumentation System Operators Manual
Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 5 15/10/2009 ADM
9
3.3 TERMINAL SPECIFICATION
Connection type
Two part connector.
•
Male part fitted to module
•
Female part supplied in module
packing case - Screw terminal,
rising clamp, no internal spring.
Example showing cable entry and screw
terminals of a 10 way connector
Minimum cable size
0.5mm² (AWG 24)
Maximum cable size
2.5mm² (AWG 10)
NOTE : For purchasing additional connector plugs from DSE, please see the section entitled
Maintenance, Spares, Repair and Servicing elsewhere in this document.
3.4 POWER SUPPLY REQUIREMENTS
Minimum supply voltage
8V continuous
Cranking dropouts
Able to survive 0V for 50mS providing the supply was at least 10V before the
dropout and recovers to 5V afterwards.
This is more than sufficient to allow the module to operate during engine
cranking where the battery supply often falls as low as 4V (on a 12V system!)
This is achieved without the need for internal batteries or other external
requirements.
Maximum supply voltage
35V continuous (60V protection for surges)
Reverse polarity protection
-35V continuous
Maximum operating current
DSE7200 / DSE7300
160mA at 24V
340mA at 12V
Maximum standby current
DSE7200 / DSE7300
80mA at 24V
160mA at 12V
Plant supply instrumentation display
Range
0V-70V DC (note Maximum continuous operating voltage of 35V DC)
Resolution
0.1V
Accuracy
±1% full scale (±0.7V)
3.5 GENERATOR AND MAINS VOLTAGE / FREQUENCY SENSING
Measurement type
True RMS conversion
Sample Rate
5KHz or better
Harmonics
Up to 10
th
or better
Input Impedance
300K
Ω
ph-N
Phase to Neutral
15V
(minimum required for sensing frequency
)
to 333V AC
(absolute maximum)
Suitable for 110V to 277V nominal
(±20% for under/overvoltage detection)
Phase to Phase
26V
(minimum required for sensing frequency
)
to 576V AC
(absolute maximum)
Suitable for 190V ph-ph to 479V ph-ph nominal
(±20% for under/overvoltage detection)
Common mode offset from Earth
100V AC (max)
Resolution
1V AC phase to neutral
2V AC phase to phase
Accuracy
±1% of full scale phase to neutral (±3.33V ph-N)
±2% of full scale phase to phase (±11.52V ph-ph)
Minimum frequency
3.5Hz
Maximum frequency
75.0Hz
Frequency resolution
0.1Hz
Frequency accuracy
±0.2Hz