Front Panel Configuration Editor (continued)
Section
Parameter as shown on display
Factory Settings
MAINS
Mains Under Voltage Trip
184V
Mains Over Voltage Trip
276V
Mains Under Frequency Trip
45Hz
Mains Over Frequency Trip
55Hz
Mains Transient Delay
2s
Return Delay
30s
Mains Transfer Time
0.7s
TIMERS
LCD Page Timer
5m
Auto Scroll Delay
3s
Pre Heat Timer
0s
Crank Duration Timer
0s
Crank Rest Timer
10s
Safety On Delay
10s
Smoke Limiting
10s
Smoke Limiting Off
0s
Warm Up Timer
0s
Cool Down Timer
0s
Speed Overshoot Delay
1m
Fail To Stop Delay
2s
Battery voltage Low Warning Delay
30s
Battery Voltage High Warning Delay
1m
Return Delay
1m
Generator Transient Delay
30s
Mains Transient Delay
0s
Mains Transfer Time
2s
Schedule
0.7s
SCHEDULE
Schedule On Load
Active, Inactive
Schedule Period
Active, Inactive (only available when Scheduler is active)
Schedule time and Date Selection (1-16)
Weekly, Monthly, (only available when Scheduler is active
Schedule time and Date Selection (1-16)
Press
to begin editing then
or
to select the different parameters in the
scheduler.