beautypg.com

Winco DSE7300 Series User Manual

Page 39

background image

DSE Model 7000 Series Control & Instrumentation System Operators Manual

Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 5 15/10/2009 ADM

39

4.3.5 DSENET®

NOTE: - This feature is only available on DSE7300 Series modules


DSENet® is the communication port between the host controller (DSE7300 series) and the expansion device as
shown below. Further details are contained within the Specification section of this documents and within the
operator manual for the specific expansion module you are connecting to.

NOTE: - This feature is not available if the DSE7300 Series module has been configured to use the

DSENet® port as the interface to Cummins Modbus Engine GCM.

NOTE:- Screened 120

impedance cable specified for use with CAN must be used for the DSENet®

(RS485) connection.

DSE stock and supply Belden cable 9841 which is a high quality 120

impedance cable suitable for

DSENet® use (DSE part number 016-030)

This manual is related to the following products: