DSE Model 7000 Series Control and Instrumentation System Operators Manual

26

Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 5 15/10/2009 ADM

4.2 TERMINAL DESCRIPTION

4.2.1 DC SUPPLY, FUEL AND START OUTPUTS

Icon

PIN

No

DESCRIPTION

CABLE

SIZE

NOTES

1

DC Plant Supply Input
(Negative)

2.5mm²

AWG 13

2

DC Plant Supply Input
(Positive)

2.5 mm²

AWG 13

(Recommended Maximum Fuse 15A anti-surge)
Supplies the module (2A anti-surge requirement) and Output
relays E,F,G & H

3

Emergency Stop Input

2.5mm²

AWG 13

Plant Supply Positive. Also supplies outputs 1 & 2.
(Recommended Maximum Fuse 20A)

4

Output relay A (FUEL)

2.5mm²

AWG 13

Plant Supply Positive from terminal 3. 15 Amp rated.
Fixed as FUEL relay if electronic engine is not configured.

5

Output relay B (START)

2.5mm²

AWG 13

Plant Supply Positive from terminal 3. 15 Amp rated.
Fixed as START relay if electronic engine is not configured.

6

Charge fail / excite

2.5mm²

AWG 13

Do not connect to ground (battery negative).
If charge alternator is not fitted, leave this terminal
disconnected.

7

Functional Earth

2.5mm²

AWG 13

Connect to a good clean earth point.

8

Output relay E

1.0mm²

AWG 18

Plant Supply Positive from terminal 2. 3 Amp rated.

9

Output relay F

1.0mm²

AWG 18

Plant Supply Positive from terminal 2. 3 Amp rated.

10

Output relay G

1.0mm²

AWG 18

Plant Supply Positive. from terminal 2. 3 Amp rated.

11

Output relay H

1.0mm²

AWG 18

Plant Supply Positive from terminal 2. 3 Amp rated.

NOTE:- Terminals 12 to 14 are not fitted to the DSE7200/DSE7300 series controller.

NOTE:- When the module is configured for operation with an electronic engine, FUEL and START

output requirements may be different. Refer to Electronic Engines and DSE Wiring for further information.
DSE Part No. 057-004.