DSE Model 7000 Series Control and Instrumentation System Operators Manual
12
Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 5 15/10/2009 ADM
3.7.4 MAGNETIC PICKUP
Type
Differential input
Minimum voltage
0.5V RMS
Max common mode voltage
±2V
Maximum voltage
Clamped to ±70V by transient suppressers, dissipation not to exceed 1W.
Maximum frequency
10,000Hz
Resolution
6.25 RPM
Accuracy
±25 RPM
Flywheel teeth
10 to 500
NOTE : DSE can supply a suitable magnetic pickup device, available in two body thread lengths :
DSE Part number 020-012 - Magnetic Pickup probe 5/8 UNF 2½” thread length
DSE Part number 020-013 - Magnetic Pickup probe 5/8 UNF 4” thread length
Magnetic Pickup devices can often be ‘shared’ between two or more devices. For example, one device can often
supply the signal to both the DSE7000 series module and the engine governor. The possibility of this depends upon
the amount of current that the magnetic pickup can supply.
3.8 OUTPUTS
3.8.1 OUTPUTS A & B
Type
Normally used for Fuel / Start outputs. Fully configurable for other purposes if the module is configured to
control an electronic engine. Supplied from Emergency Stop terminal 3.
Rating
15A resistive @ 35V
3.8.2 OUTPUTS C & D
Type
Voltage free relays, fully configurable, normally used for generator / mains load switch control.
Rating
8A resistive @ 250 V AC
3.8.3 OUTPUTS E,F,G & H
Type
Fully configurable, supplied from DC supply terminal 2.
Rating
3A resistive @ 35V