4 | PIR Ready VT76x7 Series-Installation Guide

Features overview

7 day schedule models, 2 or 4 events

Gas/oil or electric system compatibility for all type of applications

Internal RH sensor and remote RH input with humidification and dehumidification
sequence of operation embedded

Remote outdoor sensing capability for added flexibility
- System mode lock out
- Humidity setpoint reset

High limit input to prevent over-humidification

Lockable keypads for tamper proofing. No need for Terminal Equipment Controller
guards

Automatic frost protection to prevents costly freeze damage

Anti short cycle and minimum on/off run time protection. Reduces wear and maximizes
life span of mechanical equipment.

Configurable digital input for added flexibility. The input can be configured as the

following:

None: No function will be associated with the input

Service: a backlit flashing Service alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is energized. It can be tied in
to the AC unit control card, which provides an alarm in case of malfunction.

Filter: a backlit flashing Filter alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is energized. It can be tied to a
differential pressure switch that monitor filters

Rem NSB: remote NSB timer clock input. Will disable the internal scheduling of
the Terminal Equipment Controller. The scheduling will now be set as per the
digital input. The menu part related to scheduling is disabled and no longer
accessible. It provides low cost setback operation via occupancy sensor or from
a dry contact

RemOVR: temporary occupancy contact. Disables all override menu function of
the Terminal Equipment Controller. . The override function is now controlled by a
manual remote momentarily closed contact. When configured in this mode, the
input operates in a toggle mode.

With this function enabled it is now possible to toggle between unoccupied &
occupied setpoints for the amount of time set by parameter (TOccTime)
temporary occupancy time.

Fan lock: used in conjunction with a local air flow sensor connected to the input.
Locks out the Terminal Equipment Controller heating and cooling action and
displays a local alarm if no air flow is detected 10 seconds after the fan (G
terminal) is energized.

Configurable smart fan operation saves energy during night mode

Non volatile EEPROM memory prevents loss of parameters during power shortage

Built in default profile set-up for easier start up and commissioning

Configurable SPST output relay on scheduling models for lighting, exhaust fan or
fresh air control

6 hour typical reserve time for clock in case of power loss

Built in proportional humidity Terminal Equipment Controller

Proportional humidity high limit when used with the analog input for supply humidity

Automatic humidity setpoint reset when outside air temperature value is used.