beautypg.com

Viconics VT7607 Installation Manual User Manual

Page 23

background image

23 | PIR Ready VT76x7 Series-Installation Guide

Channel
Channel selection
Default value = 10
Range is: 10 to 26

Conditional parameter to Wireless models
(VT76xxX5x00W)


This parameter will only appear when a wireless network
adapter is present. If the Terminal Equipment Controller is
installed as a stand-alone

(Network Ready)

unit or with a

BACnet™ or Echelon™ adapter, this parameter will not be
used or displayed

This parameter (Channel) is used to link specific Terminal
Equipment Controllers to specific Viconics wireless
gateway(s) (VWG) For every Terminal Equipment Controller
reporting to a gateway (maximum of 30 Terminal Equipment
Controllers per gateway), be sure you set the SAME channel
value both at the gateway and the Terminal Equipment
Controller(s).

Viconics recommends using only the usage of channels
15 and 25 only

The default value of 10 is NOT a valid channel. The valid
range of available channel is from 11 to 26

Get From
Terminal Equipment
Controller Get From
another device
configuration utility
Default value = 0
Range is: 0 to 254

Conditional parameter to Wireless models
VTR73xxX5x00W
Entering a MAC address enables an automatic routine that
automatically fetches all the required configuration properties
of the current device from another already configured device
and copies the same required configured property values.
If a value other than the default value of 255 is entered, user
will then be prompted to exit the Configuration Menu thus
leaving all other parameter configuration to be copied from the
referenced Terminal Equipment Controller MAC address.

Ex.: If you are currently configuring MAC12 and the settings
matches exactly the settings of ZN MAC5, then enter 5 as the
current parameter value.

If the process is successful and all required configuration
properties have been copied, the value will revert back to
255

If the process is NOT successful and all required
configuration properties have NOT been copied ( either
the reference device is NOT the same model number or is
offline or does not exists ) the value will revert back to 254
to indicate the failure of the process

Leaving the Get From parameter to 255 means that every
configuration parameters will be set manually.

% RH disp
Local RH Display
Default value = Off

Enables the display of humidity below the room temperature on
the display

On = Display %RH

Off = No display of %RH

This manual is related to the following products: