beautypg.com

Troubleshooting guide – Viconics VT7607 Installation Manual User Manual

Page 32

background image

32 | PIR Ready VT76x7 Series-Installation Guide

RE SP

Reset humidity

setpoint

Default value =

20% RH

The RH setpoint will be reset from the user setpoint to this value

when the RH LT outside air temperature value is reached.

Only valid if an outdoor air sensor is connected at the Terminal

Equipment Controller or a network value is transmitted to the

Terminal Equipment Controller. See RH LT & RE HT.

From 10% RH up to 90% RH

RH cal

Humidity sensor

calibration

Default value = 0

%RH

Offset that can be added/subtracted to actual displayed humidity by ±

15.0 %RH.

This calibration applies to the internal humidity sensor if no remote

humidity sensor is connected. This calibration applies to the remote

humidity sensor when one is connected.

From

–15% RH up to 15% RH

Display HL

Display the high

limit sensor value

Used as diagnostic / service help to troubleshoot and diagnose

sensor / humidifier operation

Note:
When the outside air sensor is not connected or is shorted, the Terminal Equipment
Controller bypasses:

The heating lockout

The cooling lockout

The dehumidification lockout

The humidity setpoint reset


T

ROUBLESHOOTING GUIDE

Symptom

Possible Cause

Corrective Action

No display on the

Terminal Equipment

Controller

Absent or

incorrect supply

voltage

1. Check power supply voltage between

C & RC to be from 19-30 VAC

2. Check for tripped fuse or circuit

breaker

Overloaded

power

transformer

Verify that the transformer used is

powerful enough (enough VA’s) to supply

all controlled devices including the

Terminal Equipment Controller

Keyboard menu does not

access all functions

Keyboard locked

Change configuration parameter

LOCKOUT to value “0” to access all

levels of the menu

Temperature setpoints

revert to original value

after a certain time period

Temporary

setpoint option

selected

1. The Terminal Equipment Controller

needs to be in Permanent setpoint

mode for the new setpoint to be kept

and memory and used all the time

2. Go to the Set temperature menu.

3. The last prompt is setpoint type. Set it

to Permanent setpoint

This manual is related to the following products: