31 | PIR Ready VT76x7 Series-Installation Guide

RH HT

Reset RH higher outside

temperature setpoint

Default value = 32°F

(0°C)

Maximum outdoor air temperature for RH setpoint reset.

Only valid if an outdoor air sensor is connected at the Terminal

Equipment Controller or a network value is transmitted to the

Terminal Equipment Controller. See RH LT & RE Sp

From 20°F up to 55°F (-6.5°C to 13°C)

HL SP

RH High limit setpoint

Default value = 85% RH

High humidity limit in the supply.

Only valid if a 0-10 VDC sensor is connected at the Terminal

Equipment Controller

– otherwise this feature is disabled

automatically.

From 50% RH up to 90% RH

Dhu OALK

Dehumidification outside

air temperature lockout

Default value = 32°F

(0°C)

Outside air temperature under which the dehumidification

sequence is disabled.

Only valid if an outdoor air sensor is connected at the Terminal

Equipment Controller or a network value is transmitted to the

Terminal Equipment Controller.

From

–40°F up to 122°F (-40°C to 50°C)

Dhu LCK

Dehumidification Lockout

Functions

Default value = On

Enables or disables the lockout functions for the

dehumidification control process of the output.

On: will restrict the dehumidification process based on the

following:

-

System mode = Needs to be Cool or Auto ( currently

operating in cooling only )

-

Low ambient room temperature protection enabled

Off: will not restrict the dehumidification process:

-

System mode = Needs to be Cool, Heat or Auto

- There is no ambient room temperature protection

enabled

DehuHyst

Dehumidification

Hysteresis

Default value = 5% RH

Dehumidification control hysteresis

Used only if dehumidification sequence is enabled.

From 2% RH up to 20% RH