22 | PIR Ready VT76x7 Series-Installation Guide

CONFIGURATION

PARAMETERS

DEFAULT VALUE

SIGNIFICANCE AND ADJUSTMENTS

PswrdSet
Configuration parameters
menu access password
Default value = 0
No password prompted

This parameter sets a password access to prevent
unauthorized access to the configuration menu parameters.
A default value of “0” will not prompt a password or lock the
access to the configuration menu.
Range is: 0 to 1000

Com Addr
Terminal Equipment
Terminal Equipment
Controller networking
address
Default value = 254
Range is: 0 to 254

Conditional parameter to

BACnet™ MS-TP models

(VT76xxX5x00B)
Conditional parameter to Wireless models (VT76xxX5x00W)

This parameter will only appear when a

BACnet™ or wireless

network adapter is present. If the Terminal Equipment Controller
is installed as a stand-alone (Network Ready) unit or with an
Echelon™ adapter, this parameter will not be used or displayed

-For

BACnet™ MS-TP models, the valid range to is from 1 to

127. Default value of 254 disables

BACnet™ communication for

the Terminal Equipment Controller.
For wireless models valid range is 0 to 254 with a maximum of
30 Terminal Equipment Controllers per VWG

PAN ID
Personal Area Network
Identification
Default value = 0
Range is: 0 to 1000


Conditional parameter to Wireless models
(VT76xxX5x00W)


This parameter will only appear when a wireless network
adapter is present. If the Terminal Equipment Controller is
installed as a stand-alone

(Network Ready)

unit or with a

BACnet™ or Echelon™ adapter, this parameter will not be
used or displayed

This parameter (Personal Area Network Identification) is
used to link specific Terminal Equipment Controllers to a
single specific Viconics wireless gateway ( VWG ) For every
Terminal Equipment Controller reporting to a gateway
( maximum of 30 Terminal Equipment Controllers per
gateway ), be sure you set the SAME PAN ID value both at
the gateway and the Terminal Equipment Controller(s).

The default value of 0 is NOT a valid PAN ID.