14 | PIR Ready VT76x7 Series-Installation Guide

Occupied setpoints adjustments

There is a default profile set in the Terminal Equipment Controller from the factory.

This enables the Terminal Equipment Controller to operate as a non-scheduling unit in
day mode operation at start up.

Default temperature

setpoints:

Default modes:

Occupied cooling setpoint =

24 °C ( 75 °F )

System mode = Auto

Occupied heating setpoint =

22 °C ( 72 °F )

Fan mode = Smart (for models with a communication

module or scheduling network

ready models)

Fan mode = Auto (for non-scheduling network ready

models)



Unoccupied cooling setpoint

= 28 °C ( 82 °F )

Unoccupied heating setpoint

= 18 °C ( 65 °F )

Default schedules:

Fahrenheit scale

Monday through Sunday

Setpoint type = permanent

Occupied time is: 12 00 AM

Unoccupied time is: 11:59 PM

There will be a 1 minute unoccupied period every night at 11:59 PM with this default
configuration.

A) Override an unoccupied period

Override
schd Y/N

This menu will appear only when the Terminal Equipment Controller is in unoccupied
mode. The unoccupied mode is enabled either by the internal timer scheduling or by a
remote NSB contact via DI1 or DI2.

If DI1 or DI2 is configured to operate as a remote temporary override contact, this menu
will be disabled.

Answering yes to this prompt will cause the Terminal Equipment Controller to go into
occupied mode for an amount of time equal to the parameter “TOccTime” (1 to 12 hours).

B) Resume regular scheduling

Cancel
ovrd Y/N

This menu does not appear in regular operation. It will appear only when the Terminal
Equipment Controller is in unoccupied override mode.

Answering “Yes” to this question will cause the Terminal Equipment Controller to resume
the regular setpoints & scheduling.