28 | PIR Ready VT76x7 Series-Installation Guide

TOccTime
Default value = 3
hours

Temporary occupancy time with occupied mode setpoints when
override function is enabled
When the Terminal Equipment Controller is in unoccupied mode,
function is enabled with either the menu or DI1 or DI2 configured as
remote override input.
0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 & 12 hours

Cal RS
Room air temperature
sensor calibration
Default value = 0.0 °F
or °C

Offset that can be added/subtracted to actual displayed room
temperature
± 5.0 °F ( ± 2.5 °C )

Cal OS
Outside air
temperature sensor
calibration
Default value = 0.0 °F
or °C

Offset that can be added/subtracted to actual displayed outside air
temperature
± 5.0 °F ( ± 2.5 °C )

H stage
Number of heating
stages. Applicable to 2
stage models only
Default value = 2
stages

Will revert the operation of 2 stages Terminal Equipment Controller
to single stage operation only when the second heating step is not
needed.
1 or 2 stages

For heat pump models, H stage is limited to 1 stage only (W1

Aux. Heat)