5 electrical operating components, 0 electrical supply and wiring (cont’d), 1 combustion air proving (pressure) switch – Reznor UDAS Unit Installation Manual User Manual
Page 20: 2 limit control, Pressure switch settings
Page 20
7.5.1 Combustion Air Proving (Pressure) Switch
The combustion air proving switch is a pressure sensitive switch that monitors air pressure
to ensure that proper combustion airflow is available. On Standard Power Ventmodels,
the switch is a single pole/normally open device which closes when a negative pressure
is sensed in the venter housing. On Separated Combustion models, the switch senses
the differential pressure between the negative pressure in the venter housing and the
pressure in the cabinet. (For switch location, see
FIGURE 18, page 30.)
On startup when the heater is cold, the sensing pressure is at the most negative level,
and as the heater and flue system warm up, the sensing pressure becomes less
negative. After the system has reached equilibrium (about 20 minutes), the sensing
pressure levels off.
If a restriction or excessive flue length or turns cause the sensing pressure to be
outside the switch setpoint, the pressure switch will function to shutoff the main burner.
The main burner will remain off until the system has cooled and/or the flue system
resistance is reduced.
The Tables on the left below list the approximate water column negative pressure
readings and switch setpoints for sea level operating conditions for Standard Power
Vent and Model heaters. The Table on the right lists the approximate water column
differential pressure readings and switch setpoints for sea level operating conditions
for Separated Combustion Model heaters.
7.5 Electrical
Operating
Components
Pressure Switch
Settings
DANGER
Safe operation of this unit requires proper venting flow. NEVER
bypass combustion air proving switch or attempt to operate the
unit without the venter running and the proper flow in the vent
system. Hazardous conditions could result. See Hazard Intensity
Levels, page 2.
Std Power
Vent
Models
Startup
Cold
Equilibrium
Hot
Setpoint OFF Setpoint
ON
Label
Color
Switch
P/N
Std Power
Vent
Models
Startup
Cold
Equilibrium
Hot
Setpoint
OFF
Setpoint
ON
Label
Color
Switch
P/N
Negative Pressure (" w.c.)
Differential Pressure (" w.c.)
30
1.0
0.8
0.4
0.6
Green
197030
30
1.0
0.8
0.65
0.8
Yellow
197028
45
1.0
0.8
0.4
0.6
Green
197030
45
1.1
0.8
0.65
0.8
Yellow
197028
60
1.0
0.8
0.5
0.7
Orange 196388
60
1.1
0.9
0.65
0.8
Yellow
197028
75
1.0
0.9
0.5
0.7
Orange 196388
75
1.1
0.9
0.65
0.8
Yellow
197028
100
0.9
0.7
0.5
0.7
Orange 196388
100
0.9
0.7
0.55
0.7
White
196362
125
0.8
0.6
0.4
0.6
Green
197030
125
0.8
0.6
0.45
0.6
Pink
197032
150, 175
0.8
0.7
0.4
0.6
Green
197030
150, 175
0.8
0.6
0.40
0.6
Green
197030
200, 225
2.2
1.5
1.1
1.3
Blue
201158
200, 225
2.2
1.5
1.10
1.3
Blue
201158
250, 300
2.3
1.6
1.1
1.3
Blue
201158
250, 300
2.3
1.6
1.10
1.3
Blue
201158
350, 400
2.6
1.8
1.1
1.6
Red
201159
350, 400
2.6
1.8
1.10
1.6
Blue
201158
Std Power Vent
Model with Opt AV6
Startup Cold Equilibrium
Hot
Setpoint
OFF
Setpoint
ON
Label
Color
Switch
P/N
Negative Pressure (" w.c.)
30
1.1
0.8
0.65
0.8
Yellow
197028
45
1.1
0.8
0.50
0.7
Orange
196388
60
0.9
0.8
0.60
0.8
Lt Blue
197029
75
1.0
0.8
0.60
0.8
Lt Blue
197029
100
0.9
0.7
0.55
0.7
White
196362
7.5.2 Limit Control
All units are equipped with a temperature activated auto reset limit control. The con-
trol is factory set and is non-adjustable. If the setpoint is reached, the limit control will
interrupt the electric supply to the gas valve. This safety device provides protection in
the case of motor failure or lack of airflow due to a restriction at the inlet or outlet. (For
location, see
FIGURE 18, page 30.)
CAUTION: The auto reset limit control will continue to shut down the
heater until the cause is corrected. Never bypass the limit control;
hazardous conditions could result. See Hazard Intensity Levels, page 2.
7.0 Electrical
Supply and
Wiring (cont’d)