Rev. 1.1
Output
Location
(hex)
LSB
Comment
Example
Watts B Max
53
mW
Maximum Outlet 2 active power
measured (per second).
If the maximum power measured on
Outlet 2 is 200 Watts
)53?
Returns:
+200.000
Irms_nb B
Min
54
mArms
Outlet 2 minimum narrowband
rms current measured.
If the smallest narrowband current
measured on Outlet 2 is 1 Amp
)54?
Returns:
+1.000
Irms_nb B
Max
55
mArms
Outlet 2 maximum narrowband
rms current measured.
If the largest narrowband current
measured on Outlet 2 is 30 Amps
)55?
Returns:
+30.000
VARs_nb B
Min
56
mW
Outlet 2 minimum narrowband
reactive power measured (per
second).
If the largest VARs measured on Outlet
2 is 80 VARs
)56?
Returns:
+80.000
VARs_nb B
Max
57
mW
Outlet 2 maximum narrowband
reactive power measured (per
second).
If the largest narrowband VARs
measured on Outlet 2 is
300 VARs
)57?
Returns:
+300.000
VAs_nb B
Min
58
mW
Outlet 2 minimum narrowband
apparent power measured (per
second)
If the smallest narrowband VAs
measured on Outlet 2 is 80 VARs
)58?
Returns:
+80.000
VAs_nb B
Max
59
mW
Outlet 2 maximum narrowband
apparent power measured (per
second).
If the largest narrowband VAs
measured on Outlet 2 is
300 VARs
)59?
Returns:
+300.000
Power
Factor_nb B
Min
5A
–
Outlet 2 minimum narrowband
power factor measured.
Minimum is defined as the
most negative or least positive
number.
If minimum narrowband power factor
measured on Outlet 2 is
-0.6
)5A?
-0.600
Power
Factor_nb B
Max
5B
–
Outlet 2 maximum narrowband
power factor measured.
Maximum is defined as the
most positive or least negative
number.
If maximum narrowband power factor
measured on Outlet 2 is 0.9
)5B?
+0.900
Phase
Angle_nb B
Min
5C
–
Outlet 2 minimum narrowband
phase angle measured.
If the minimum narrowband phase
angle measured on Outlet 2 is 10
degrees
)5C?
Returns:
+10.000