PXL-100:SMART ENTRY CONTROLLER
11) Specifications and System Requirements
Controller Architecture - Single door networkable access control system
System Configuration - Accomplished with either the TAP-100 DOS based software or the HPP-100
Hand Held Programmer.
System Capacity - Controllers - From 1 to 32 controllers (1 to 64 Doors if using in conjunctions with
an OB-9 2nd Door Control Option Board)
- Cardholders - 7000 cards stored locally at each controller
- Transactions - 3000 events stored locally at each controller
- Time Zones - 32 distinct time zones
- Holidays - 20 Days
Outputs - RS-232 serial port for external communications to PC, modem or printer
- RS-485 network communications when not using the system in stand alone mode
- General purpose inputs and outputs are configurable depending on system setup
Memory Retention - 5 year battery back up of RAM
Power Requirements - 12 VAC @20VA or 12VDC @1.5 Amp
Power Output -12VDC for lock power, 400 mA max, Relay (formerly open collector on design 4 units)
Current Draw - Not to exceed 900mA (including PXL-100, Reader, and Door Strike)
- PXL-100 + Option Board (400mA max)
- MS-3000/MS-5000/KDF-3E/KWS-5E (100mA max), KMI-20E/KME-22E (250mA max)
Relay Contact Rating - 32VAC @ 5Amp max
24VDC @ 2Amp max
Inputs - Door Sense
- Normally Closed
- REX
- Normally Open
- Gen Purpose
- Normally Closed
Printer Requirements - Serial RS-232
2400 BAUD
8 Bit , no parity
1 stop bit
PC Requirements - IBM Compatible, 386 or better, Color monitor, 20 megabyte hard drive and 1
Mbyte of RAM and 520KB free of conventional memory. Keri recommends
installing and running the software from the hard drive.
12) Cable and Wiring Requirements
Cable Requirements for Readers - Readers (Belden 9536, 22AWG or equivalent. Larger guages
should be used for longer distances.)
Reader Type
Length with 24AWG
Length with 22 AWG
KDF-3E, KWS-5E
450'
600'
MS-3000, MS-5000
350'
500'
KSI-10E, KSE-12E
350'
500'
KMI-20E, KME-22E
300'
450'