beautypg.com

Quick start guide – Keri Systems PXL-510 User Manual

Page 5

background image

PXL-500 / PXL-510 Tiger Controller

Quick Start Guide

Page 5 of 24

P/N: 01918-001 Rev. B

DO NOT

make modem phone line connections through PBX telephone switching systems - most modems are not compatible

with PBX systems leading to disconnection problems with the modem

locate the PXL-500/PXL-510 controller near EMI sources - EMI sources can affect the performance of the controller

use switching power supplies - they are EMI sources

route network and reader cables beside power cables - transients on the power cables may be picked-up by network

and reader cables

stretch or over-tension cables

route over sharp objects

let the wires get tangled

mix PXL-500s/PXL-510s with PXL-100s in the same network

use a PXL-250 as the master on a network with PXL-500s/PXL-510s. The PXL-500/PXL-510 should always be the

master controller.

route controllers in a network in a loop configuration

connect earth ground

1

to the network cable shield - the PXL-500/PXL-510 automatically connects earth ground to the

shield at one point on the network to prevent ground loops

use gender changer plugs when making RS-232 serial communication connections (unless you know it is a “straight-

through” plug) - gender changers may have internal wiring changes that can disrupt communications

This manual is related to the following products: