Power connection guidelines for dc-powered routers – Cisco XR 12406 User Manual
Page 80

Chapter 2 Preparing for Installation
Installation Site Requirements
2-16
Cisco XR 12406 Router Installation Guide
OL-13831-01
Figure 2-3
AC Power Plugs
Power Connection Guidelines for DC-Powered Routers
When the Cisco XR 12406 Router operates with a DC PDU, observe these
guidelines:
•
A Cisco XR 12406 Router configured with a DC PDU and DC-input PEMs
require a dedicated 45A DC circuit breaker for each DC power source. This
circuit breaker protects against short-circuit and overcurrent faults in
accordance with United States National Electrical Code NFPA 70 (United
States), Canadian Electrical Code, part I, CSA C22.1 (Canada), and IEC 364
(other countries).
•
DC power cable leads should be #6 American Wiring Gauge (AWG)
high-strand-count wire.
•
Provide a dedicated power source for each power entry module installed in
the router.
•
Install an uninterruptable power source where possible.
57648
North American plug
L6-20 20A
Australian plug
AS 3112 15A
European plug
CEE 7/7 16A
Italian plug
CEI 23-16/VII 16A
United Kingdom plug
BS 1363 13A