Removing and replacing a dc pem – Cisco XR 12406 User Manual
Page 190

Chapter 5 Maintaining the Router
Removing and Replacing a DC PEM
5-26
Cisco XR 12406 Router Installation Guide
OL-13831-01
Step 14
Set the power switch on both power supplies to the on (1) position.
The AC Input Power and DC Output Power indicators on the power supplies
should be on. If the indicators do are not on, see the
Power Entry Module Installation” section on page 5-17
.
Removing and Replacing a DC PEM
Although a DC PEM supports OIR, in order to maintain operational redundancy,
proper cooling, and meet EMI compliance standards, you must have both working
power supplies installed. When you remove a failed power supply with the router
in operation, perform the replacement as quickly as possible. Make sure you have
the tools and the replacement power supply ready before beginning the removal
and installation procedure.
Use the following procedure to remove and replace a DC PEM.
- ASA 5505 (1994 pages)
- OL-15491-01 (268 pages)
- WUSB600N (43 pages)
- 10000 (556 pages)
- 10000 (12 pages)
- 3825 (358 pages)
- WRV54G (101 pages)
- WUSB54GC (33 pages)
- 2600 Series (10 pages)
- DPQ2202 (38 pages)
- 1600 (13 pages)
- WRT320N (53 pages)
- 1701 (10 pages)
- 300 (16 pages)
- 3200 Series (60 pages)
- 2900 SERIES XL (138 pages)
- 4430 (12 pages)
- 1005 (6 pages)
- 3500 Series (8 pages)
- GigaStack WS-X3500-XL (58 pages)
- WIRELESS-G WRT54GP2 (112 pages)
- 1604 (22 pages)
- 3600 Series (18 pages)
- WIRELESS LAN CONTROLLER OL-17037-01 (80 pages)
- DPC3000 (36 pages)
- 3545 MCU (56 pages)
- WRT110 (48 pages)
- 7300-6T3 (54 pages)
- 10BASE-FL (40 pages)
- 340 (62 pages)
- 1700 (88 pages)
- 1700 (14 pages)
- 12000 (60 pages)
- 3600 (18 pages)
- 1800 Series (12 pages)
- 2000 (6 pages)
- ACE XML OL-13877-01 (12 pages)
- 10720 (26 pages)
- 10008 (38 pages)
- 10008 (48 pages)
- 1-PORT G.SHDSL 2600 (22 pages)
- XM Universal Gateways Cisco AS5400XM (100 pages)
- 1710 (12 pages)
- WRTP54G (114 pages)
- 7201 (4 pages)