C-PRO NANO HARDWARE MANUAL
Page 18
C1-12 COMMON DO6
Relay No.6 - common
Connector 2:
Connector for low voltage signals
Conn.
Abbrev.
Description
C2-1
12 V AC (Power)
Device power supply (12 V AC/DC)
C2-2
Not connected
Not connected
C2-3
GND
Common analogue and digital inputs
C2-4
GND
Common analogue and digital inputs
C2-5
AI4
Analogue input No. 4 (for NTC probes or for 0/4-20 mA or 0-5V
transducers)
C2-6
AI3
Analogue input No. 3 (for NTC probes or for 0/4-20 mA or 0-5V
transducers)
C2-7
AI2
Analogue input No. 2 (for NTC probes)
C2-8
AI1
Analogue input No. 1 (for NTC probes)
C2-9
12 V AC (Power)
Device power supply (12 V AC/DC)
C2-10 12 V DC
Current transducer and cut-off module power supply (50 mA max.
not protected against short circuits)
C2-11 AO1
Cut-off module impulse output
C2-12 DI5
Digital input No. 5
C2-13 DI4
Digital input No. 4
C2-14 DI3
Digital input No. 3
C2-15 DI2
Digital input No. 2
C2-16 DI1
Digital input No. 1
Connector 3:
Connector to the controller (IntraBus)
Conn.
Abbrev.
Description
C3-1
VDC
Power supply
C3-2
GND
Common
C3-3
DATA
Powered serial connection
Connector 3:
Connector to the controller (CAN)
Conn.
Abbrev.
Description
C3-1
+
Connector for the serial CAN + connection
C3-2
GND
Ground reference connector
C3-3
-
Connector for the serial CAN - connection