LABEL

MIN. MAX. U.M.

DEF. ERASING OF THE DATA THE INSTRUMENT HAS STORED

Delete Memory?

Yes

No

---

No

(6)

erasing of the data the instrument has stored

Memory Type

0

1

---

0

data control when the memory has run out (0 = the instrument will not store

any data, 1 = the instrument will erase the oldest data in order to store the

new ones)

(7)

Delete Auto

Yes

No

---

No

erasing of the data the instrument has stored after you have printed them

during the Historical Report printing mode

LABEL

MIN. MAX. U.M.

DEF. MEASURE INPUTS NUMBER

N. Probe

1

6

---

2

measure inputs number

LABEL

MIN. MAX. U.M.

DEF. MEASURE INPUT 1

AN1 Type

---

---

---

PTC

kind of probe 1 (PTC, TC J, TC K, NTC, 4-20mA, PT 100)

AN1 Alarm Setup

---

---

---

No

kind of alarm (No = it will never be activated, AL = lower alarm,

AH = upper alarm, AH & AL = both the upper alarm and the lower one)

AN1 Max Alarm

-99

999

(8)

70

upper alarm threshold (it is important if AN1 Alarm Setup = AH or AH & AL)

AN1 Min Alarm

-99

999

(8)

10

lower alarm threshold (it is important if AN1 Alarm Setup = AL or AH & AL)

AN1 Alarm Hyst

1

20

(8)

2

hysteresis (differential, it is relative to AN1 Max Alarm and AN1 Min Alarm,

it is important if AN1 Alarm Setup ≠ No)

AN1 Offset

-20

20

(8)

0

probe 1 calibration

AN1 4-20mA Type

---

---

---

%RH 4-20 mA unit of measure (it is important if AN1 Type = 4-20 mA;

RH% = percentage of relative humidity, bar = bar, °C = Celsius degree,

°F = Fahrenheit degree, Hz = hertz, mA = milliampere, - = dimensionless)

AN1 4-20mA Min

-99

999

points

0

minimum value of the range of the transducer 1 (it is important if

AN1 Type

= 4-20 mA)

AN1 4-20mA Max

-99

999

points

100

maximum value of the range of the transducer 1 (it is important if

AN1 Type

= 4-20 mA)

AN1 dec. point

0

2

---

0

decimal point position (it is important if AN1 Type = 4-20 mA;

0 = it will never be showed, 1 = ten, 2 = hundred)

LABEL

MIN. MAX. U.M.

DEF. MEASURE INPUT 2

AN2 Type

---

---

---

PTC

kind of probe 2 (PTC, TC J, TC K, NTC, 4-20mA, PT 100)

(9)

AN2 Alarm Setup

---

---

---

No

kind of alarm (No = it will never be activated, AL = lower alarm,

AH = upper alarm, AH & AL = both the upper alarm and the lower one)

(9)

AN2 Max Alarm

-99

999

(10)

70

upper alarm threshold (it is important if AN2 Alarm Setup = AH or AH & AL)

(9)

AN2 Min Alarm

-99

999

(10)

10

lower alarm threshold (it is important if AN2 Alarm Setup = AL or AH & AL)

(9)

AN2 Alarm Hyst

1

20

(10)

2

hysteresis (differential, it is relative to AN2 Max Alarm and AN2 Min Alarm,

it is important if AN2 Alarm Setup ≠ No)

(9)

AN2 Offset

-20

20

(10)

0

probe 2 calibration

(9)

AN2 4-20mA Type

---

---

---

%RH

4-20 mA unit of measure (it is important if AN2 Type = 4-20 mA;

RH% = percentage of relative humidity, bar = bar, °C = Celsius degree,

°F = Fahrenheit degree, Hz = hertz, mA = milliampere, - = dimensionless)

(9)

AN2 4-20mA Min

-99

999

points

0

minimum value of the range of the transducer 2 (it is important if

AN2 Type

= 4-20 mA)

(9)

AN2 4-20mA Max

-99

999

points

100

maximum value of the range of the transducer 2 (it is important if

AN2 Type

= 4-20 mA)

(9)

AN2 dec. point

0

2

---

0

decimal point position (it is important if AN2 Type = 4-20 mA;

0 = it will never be showed, 1 = ten, 2 = hundred)

(9)

LABEL

MIN. MAX. U.M.

DEF. MEASURE INPUT 3

AN3 Type

---

---

---

PTC

kind of probe 3 (PTC, TC J, TC K, NTC, 4-20mA, PT 100)

(11)

AN3 Alarm Setup

---

---

---

No

kind of alarm (No = it will never be activated, AL = lower alarm,

AH = upper alarm, AH & AL = both the upper alarm and the lower one)

(11)

AN3 Max Alarm

-99

999

(12)

70

upper alarm threshold (it is important if AN3 Alarm Setup = AH or AH & AL)

(11)

AN3 Min Alarm

-99

999

(12)

10

lower alarm threshold (it is important if AN3 Alarm Setup = AL or AH & AL)

(11)

AN3 Alarm Hyst

1

20

(12)

2

hysteresis (differential, it is relative to AN3 Max Alarm and AN3 Min Alarm,

it is important if AN3 Alarm Setup ≠ No)

(11)

AN3 Offset

-20

20

(12)

0

probe 3 calibration

(11)

AN3 4-20mA Type

---

---

---

%RH 4-20 mA unit of measure (it is important if AN3 Type = 4-20 mA;

RH% = percentage of relative humidity, bar = bar, °C = Celsius degree,

°F = Fahrenheit degree, Hz = hertz, mA = milliampere, - = dimensionless)

(11)

AN3 4-20mA Min

-99

999

points

0

minimum value of the range of the transducer 3 (it is important if

AN3 Type

= 4-20 mA)

(11)

AN3 4-20mA Max

-99

999

points

100

maximum value of the range of the transducer 3 (it is important if

AN3 Type

= 4-20 mA)

(11)

AN3 dec. point

0

2

---

0

decimal point position (it is important if AN3 Type = 4-20 mA;

0 = it will never be showed, 1 = ten, 2 = hundred)

(11)

LABEL

MIN. MAX. U.M.

DEF. MEASURE INPUT 4

AN4 Type

---

---

---

PTC

kind of probe 4 (PTC, TC J, TC K, NTC, 4-20mA, PT 100)

(13)

AN4 Alarm Setup

---

---

---

No

kind of alarm (No = it will never be activated, AL = lower alarm,

AH = upper alarm, AH & AL = both the upper alarm and the lower one)

(13)

AN4 Max Alarm

-99

999

(14)

70

upper alarm threshold (it is important if AN4 Alarm Setup = AH or AH & AL)

(13)

AN4 Min Alarm

-99

999

(14)

10

lower alarm threshold (it is important if AN4 Alarm Setup = AL or AH & AL)

(13)

AN4 Alarm Hyst

1

20

(14)

2

hysteresis (differential, it is relative to AN4 Max Alarm and AN4 Min Alarm,

it is important if AN4 Alarm Setup ≠ No)

(13)

AN4 Offset

-20

20

(14)

0

probe 4 calibration

(13)