EVCO PR100AX9S001 User Manual
Page 6

LABEL
MIN. MAX. U.M.
DEF. ERASING OF THE DATA THE INSTRUMENT HAS STORED
Delete Memory?
Yes
No
---
No
(6)
erasing of the data the instrument has stored
Memory Type
0
1
---
0
data control when the memory has run out (0 = the instrument will not store
any data, 1 = the instrument will erase the oldest data in order to store the
new ones)
(7)
Delete Auto
Yes
No
---
No
erasing of the data the instrument has stored after you have printed them
during the Historical Report printing mode
LABEL
MIN. MAX. U.M.
DEF. MEASURE INPUTS NUMBER
N. Probe
1
6
---
2
measure inputs number
LABEL
MIN. MAX. U.M.
DEF. MEASURE INPUT 1
AN1 Type
---
---
---
PTC
kind of probe 1 (PTC, TC J, TC K, NTC, 4-20mA, PT 100)
AN1 Alarm Setup
---
---
---
No
kind of alarm (No = it will never be activated, AL = lower alarm,
AH = upper alarm, AH & AL = both the upper alarm and the lower one)
AN1 Max Alarm
-99
999
(8)
70
upper alarm threshold (it is important if AN1 Alarm Setup = AH or AH & AL)
AN1 Min Alarm
-99
999
(8)
10
lower alarm threshold (it is important if AN1 Alarm Setup = AL or AH & AL)
AN1 Alarm Hyst
1
20
(8)
2
hysteresis (differential, it is relative to AN1 Max Alarm and AN1 Min Alarm,
it is important if AN1 Alarm Setup ≠ No)
AN1 Offset
-20
20
(8)
0
probe 1 calibration
AN1 4-20mA Type
---
---
---
%RH 4-20 mA unit of measure (it is important if AN1 Type = 4-20 mA;
RH% = percentage of relative humidity, bar = bar, °C = Celsius degree,
°F = Fahrenheit degree, Hz = hertz, mA = milliampere, - = dimensionless)
AN1 4-20mA Min
-99
999
points
0
minimum value of the range of the transducer 1 (it is important if
AN1 Type
= 4-20 mA)
AN1 4-20mA Max
-99
999
points
100
maximum value of the range of the transducer 1 (it is important if
AN1 Type
= 4-20 mA)
AN1 dec. point
0
2
---
0
decimal point position (it is important if AN1 Type = 4-20 mA;
0 = it will never be showed, 1 = ten, 2 = hundred)
LABEL
MIN. MAX. U.M.
DEF. MEASURE INPUT 2
AN2 Type
---
---
---
PTC
kind of probe 2 (PTC, TC J, TC K, NTC, 4-20mA, PT 100)
(9)
AN2 Alarm Setup
---
---
---
No
kind of alarm (No = it will never be activated, AL = lower alarm,
AH = upper alarm, AH & AL = both the upper alarm and the lower one)
(9)
AN2 Max Alarm
-99
999
(10)
70
upper alarm threshold (it is important if AN2 Alarm Setup = AH or AH & AL)
(9)
AN2 Min Alarm
-99
999
(10)
10
lower alarm threshold (it is important if AN2 Alarm Setup = AL or AH & AL)
(9)
AN2 Alarm Hyst
1
20
(10)
2
hysteresis (differential, it is relative to AN2 Max Alarm and AN2 Min Alarm,
it is important if AN2 Alarm Setup ≠ No)
(9)
AN2 Offset
-20
20
(10)
0
probe 2 calibration
(9)
AN2 4-20mA Type
---
---
---
%RH
4-20 mA unit of measure (it is important if AN2 Type = 4-20 mA;
RH% = percentage of relative humidity, bar = bar, °C = Celsius degree,
°F = Fahrenheit degree, Hz = hertz, mA = milliampere, - = dimensionless)
(9)
AN2 4-20mA Min
-99
999
points
0
minimum value of the range of the transducer 2 (it is important if
AN2 Type
= 4-20 mA)
(9)
AN2 4-20mA Max
-99
999
points
100
maximum value of the range of the transducer 2 (it is important if
AN2 Type
= 4-20 mA)
(9)
AN2 dec. point
0
2
---
0
decimal point position (it is important if AN2 Type = 4-20 mA;
0 = it will never be showed, 1 = ten, 2 = hundred)
(9)
LABEL
MIN. MAX. U.M.
DEF. MEASURE INPUT 3
AN3 Type
---
---
---
PTC
kind of probe 3 (PTC, TC J, TC K, NTC, 4-20mA, PT 100)
(11)
AN3 Alarm Setup
---
---
---
No
kind of alarm (No = it will never be activated, AL = lower alarm,
AH = upper alarm, AH & AL = both the upper alarm and the lower one)
(11)
AN3 Max Alarm
-99
999
(12)
70
upper alarm threshold (it is important if AN3 Alarm Setup = AH or AH & AL)
(11)
AN3 Min Alarm
-99
999
(12)
10
lower alarm threshold (it is important if AN3 Alarm Setup = AL or AH & AL)
(11)
AN3 Alarm Hyst
1
20
(12)
2
hysteresis (differential, it is relative to AN3 Max Alarm and AN3 Min Alarm,
it is important if AN3 Alarm Setup ≠ No)
(11)
AN3 Offset
-20
20
(12)
0
probe 3 calibration
(11)
AN3 4-20mA Type
---
---
---
%RH 4-20 mA unit of measure (it is important if AN3 Type = 4-20 mA;
RH% = percentage of relative humidity, bar = bar, °C = Celsius degree,
°F = Fahrenheit degree, Hz = hertz, mA = milliampere, - = dimensionless)
(11)
AN3 4-20mA Min
-99
999
points
0
minimum value of the range of the transducer 3 (it is important if
AN3 Type
= 4-20 mA)
(11)
AN3 4-20mA Max
-99
999
points
100
maximum value of the range of the transducer 3 (it is important if
AN3 Type
= 4-20 mA)
(11)
AN3 dec. point
0
2
---
0
decimal point position (it is important if AN3 Type = 4-20 mA;
0 = it will never be showed, 1 = ten, 2 = hundred)
(11)
LABEL
MIN. MAX. U.M.
DEF. MEASURE INPUT 4
AN4 Type
---
---
---
PTC
kind of probe 4 (PTC, TC J, TC K, NTC, 4-20mA, PT 100)
(13)
AN4 Alarm Setup
---
---
---
No
kind of alarm (No = it will never be activated, AL = lower alarm,
AH = upper alarm, AH & AL = both the upper alarm and the lower one)
(13)
AN4 Max Alarm
-99
999
(14)
70
upper alarm threshold (it is important if AN4 Alarm Setup = AH or AH & AL)
(13)
AN4 Min Alarm
-99
999
(14)
10
lower alarm threshold (it is important if AN4 Alarm Setup = AL or AH & AL)
(13)
AN4 Alarm Hyst
1
20
(14)
2
hysteresis (differential, it is relative to AN4 Max Alarm and AN4 Min Alarm,
it is important if AN4 Alarm Setup ≠ No)
(13)
AN4 Offset
-20
20
(14)
0
probe 4 calibration
(13)