Digital inputs: 1 for remote print (NO contact) without voltage (it works with 5 mA).

Working range: from -45 to 150 °C (-49 to 302 °F) for PTC probe, from -20 to 110 °C

(-4 to 230 °F) for NTC probe, from -100 to 700 °C (-148 to 1,292 °F) for “J” thermocou-

ple (if the cold joint is at 0 °C), from -100 to 1,300 °C (-148 to 2,372 °F) for “K” thermo-

couple (if the cold joint is at 0 °C), from -100 to 600 °C (-148 to 1,112 °F) for 2 wires

Pt 100 probe.

Resolution: 1 °F with unit of measure in Fahrenheit, 1 °C with unit of measure in

Celsius, 1% of relative humidity, 1 bar.

Display: one green LCD (2 lines per 16 characters) 11.5 mm (0.45 in) high, instrument

mode indicators.

Maximum size of the roll of paper: 58 x Ø 30 mm (2.28 x Ø 1.18 in).

Print width: 48 mm (1.88 in).

Dot number (for every line): 384.

Print density: 8 dot per mm.

AN6 4-20mA Type

---

---

---

%RH

4-20 mA unit of measure (it is important if AN6 Type = 4-20 mA;

RH% = percentage of relative humidity, bar = bar, °C = Celsius degree,

°F = Fahrenheit degree, Hz = hertz, mA = milliampere, - = dimensionless)

(17)

AN6 4-20mA Min

-99

999

points

0

minimum value of the range of the transducer 6 (it is important if

AN6 Type

= 4-20 mA)

(17)

AN6 4-20mA Max

-99

999

points

100

maximum value of the range of the transducer 6 (it is important if

AN6 Type

= 4-20 mA)

(17)

AN6 dec. point

0

2

---

0

decimal point position (it is important if AN6 Type = 4-20 mA;

0 = it will never be showed, 1 = ten, 2 = hundred)

(17)

(4)

if the parameter has value Yes, the instrument will print the set up as soon as you will quit the configuration parameters setting procedure

(5)

in order to activate the Daily Report printing mode, the parameter Off Line must have value Yes and the parameter Print Hour must have values different from Off; in order

to activate the Historical Report printing mode, the parameter Off Line must have value Yes

(6)

as soon as you will quit the configuration parameters setting procedure, the parameter will automatically get value No

(7)

if you modify the value of the parameter, this will erase the data the instrument has stored

(8)

the unit of measure depends on the parameters AN1 Type, Celsius/Fahr. and AN1 4-20mA Type

(9)

unless the parameter N. Probe has value 2, the parameter will not be showed

(10) the unit of measure depends on the parameters AN2 Type, Celsius/Fahr. and AN2 4-20mA Type

(11) unless the parameter N. Probe has value 3, the parameter will not be showed

(12) the unit of measure depends on the parameters AN3 Type, Celsius/Fahr. and AN3 4-20mA Type

(13) unless the parameter N. Probe has value 4, the parameter will not be showed

(14) the unit of measure depends on the parameters AN4 Type, Celsius/Fahr. and AN4 4-20mA Type

(15) unless the parameter N. Probe has value 5, the parameter will not be showed

(16) the unit of measure depends on the parameters AN5 Type, Celsius/Fahr. and AN5 4-20mA Type

(17) unless the parameter N. Probe has value 6, the parameter will not be showed

(15) the unit of measure depends on the parameters AN6 Type, Celsius/Fahr. and AN6 4-20mA Type.