3.

ELECTRICAL CONNECTION

3.1.

Electrical connection

Position micro-switch 4 on position ON to plug in the termination of the CAN port; micro-switches 1, 2 and 3 are reserved.

The following tables show the meaning of the connectors.

Connector 1:

CAN port.

Terminal

Meaning

1

ground

2

signal +

3

signal -

The maximum length of the connecting cables of the CAN port of the interface depends on the baud rate of the CAN communication, as

follows:

-

1,000 m (3,280 ft) with baud rate 20,000 baud

-

500 m (1,640 ft) with baud rate 50,000 baud

-

250 m (820 ft) with baud rate 125,000 baud

-

50 m (164 ft) with baud rate 500,000 baud.

Connect the CAN port of the interface using a twisted pair.

According to the default settings, the interface recognizes the baud rate automatically, on condition that it is one of the those mentioned above;

hereinafter one suggests setting the same baud rate of the others devices in the network.

Connector 2:

power supply (not isolated 24 VAC or 20 ... 40 VDC or isolated 12-24 VAC or 15 ... 40 VDC, according to the model).