Electrical connection – EVCO EPV4GBR Hardware manual User Manual
Page 8
Evco S.p.A.
Vgraph | Hardware manual ver. 1.01 | Code 114VGRAHWE01
page 8 of 22
3.
ELECTRICAL CONNECTION
3.1.
Electrical connection
Position micro-switch 4 on position ON to plug in the termination of the CAN port; micro-switches 1, 2 and 3 are reserved.
The following tables show the meaning of the connectors.
Connector 1:
CAN port.
Terminal
Meaning
1
ground
2
signal +
3
signal -
The maximum length of the connecting cables of the CAN port of the interface depends on the baud rate of the CAN communication, as
follows:
-
1,000 m (3,280 ft) with baud rate 20,000 baud
-
500 m (1,640 ft) with baud rate 50,000 baud
-
250 m (820 ft) with baud rate 125,000 baud
-
50 m (164 ft) with baud rate 500,000 baud.
Connect the CAN port of the interface using a twisted pair.
According to the default settings, the interface recognizes the baud rate automatically, on condition that it is one of the those mentioned above;
hereinafter one suggests setting the same baud rate of the others devices in the network.
Connector 2:
power supply (not isolated 24 VAC or 20 ... 40 VDC or isolated 12-24 VAC or 15 ... 40 VDC, according to the model).
Terminal
Meaning
4
power supply
5
power supply