Power supply:

according to the model:

-

12-24 VAC (min. 11.4 VAC, max. 27.6 VAC), 50/60 Hz, 3 VA (approximate) isolated or

15 ... 40 VDC, 3 W (approximate) isolated

-

24 VAC (min. 20.4 VAC, max. 27.6 VAC), 50/60 Hz, 3 VA (approximate) non isolated or

20 ... 40 VDC, 2 W (approximate) non isolated

supplied from a class 2 circuit.

The maximum length of the connecting cables of the power supply is 10 m (32.8 ft).

In the models with not isolated power supply, this must galvanically be isolated from the one of the

other devices connected in the network.

Protect the power supply with an UL listed or recognized fuse rated:

-

80 mA-T if the user interface is powered with 15... 40 VDC

-

160 mA-T if the user interface is powered with 12... 19 VAC

-

125 mA-T if the user interface is powered with 19... 24 VAC.

Overvoltage category:

III.

Real time clock data maintenance in

absence of power supply:

2 days will battery fully charged; the real time clock is available by request.

Battery charging time

2 min without interruptions (the battery is charged by the power supply of the interface).

Alarm buzzer:

by request.

Display:

128 x 64 pixel single colour LCD graphic display (black with rearlighting through white LED).

Communication ports:

2 ports:

-

1 non optoisolated CAN port

-

1 programming port.