EVCO EPV4GBR Hardware manual User Manual
Page 13
Evco S.p.A.
Vgraph | Hardware manual ver. 1.01 | Code 114VGRAHWE01
page 13 of 22
CAN Network
MyNode
1
127
- - -
99
Local (or of the interface) CAN node’s address
CAN Network
Master
- - -
- - -
- - -
YES
The interface always works as master
CAN Network
Baud
- - -
- - -
- - -
Auto
CAN communication baud rate
20K
=
20,000 baud
50K
=
50,000 baud
125K
=
125,000 baud
500K
=
500.000 baud
Auto
=
the interface recognizes the baud
rate automatically, on condition
that it is one of the those
mentioned above
CAN Network
Net Timeout
1
240
s
5
Remote (or of the devices in the network) CAN
communication time-out (after this time without
CAN communication with a device, this will be
excluded by the network)
CAN Network
NW Node
[1] 1
[32] 127
- - -
- - -
Remote (or of the devices in the network) CAN
nodes’ address; example for [1] 2:
[1]
=
node
2
=
node’s address
Modbus
Address
1
247
- - -
1
Modbus address (reserved)
Modbus
Parity
- - -
- - -
- - -
even
Modbus communication parity (reserved)
none
=
no parity
odd
=
odd
even
=
even
Modbus
Baudrate
- - -
- - -
- - -
9600
Modbus communication baud rate (reserved)
1200
=
1,200 baud
2400
=
2,400 baud
4800
=
4,800 baud
9600
=
9,600 baud
19200
=
19,200 baud
28800
=
28,800 baud
38400
=
38,400 baud
57600
=
57,600 baud
Modbus
Bit Stop
- - -
- - -
- - -
1 bit
Modbus communication
stop bit
number
(reserved)