Evco S.p.A.

Vgraph | Hardware manual ver. 1.01 | Code 114VGRAHWE01

page 13 of 22

CAN Network

MyNode

1

127

- - -

99

Local (or of the interface) CAN node’s address

CAN Network

Master

- - -

- - -

- - -

YES

The interface always works as master

CAN Network

Baud

- - -

- - -

- - -

Auto

CAN communication baud rate

20K

=

20,000 baud

50K

=

50,000 baud

125K

=

125,000 baud

500K

=

500.000 baud

Auto

=

the interface recognizes the baud

rate automatically, on condition

that it is one of the those

mentioned above

CAN Network

Net Timeout

1

240

s

5

Remote (or of the devices in the network) CAN

communication time-out (after this time without

CAN communication with a device, this will be

excluded by the network)

CAN Network

NW Node

[1] 1

[32] 127

- - -

- - -

Remote (or of the devices in the network) CAN

nodes’ address; example for [1] 2:

[1]

=

node

2

=

node’s address

Modbus

Address

1

247

- - -

1

Modbus address (reserved)

Modbus

Parity

- - -

- - -

- - -

even

Modbus communication parity (reserved)

none

=

no parity

odd

=

odd

even

=

even

Modbus

Baudrate

- - -

- - -

- - -

9600

Modbus communication baud rate (reserved)

1200

=

1,200 baud

2400

=

2,400 baud

4800

=

4,800 baud

9600

=

9,600 baud

19200

=

19,200 baud

28800

=

28,800 baud

38400

=

38,400 baud

57600

=

57,600 baud

Modbus

Bit Stop

- - -

- - -

- - -

1 bit

Modbus communication

stop bit

number

(reserved)