Section 7

• The motor should be accelerated and decelerated slowly to determine that the

motor and the mounting base do not vibrate abnormally.

4.

Frequency and fault indicator:

Operating status and fault status are displayed by the three^igit seven-segment

LCD on the printed circuit board.

TABLE 6

Otsp(«y Item

Display Condition and Content

Display

Example

When «12 Jumper is It.

Displayed with one decimal digit. 0.5 to 60.0.

80.0

Output

Frequency

When J2 Jumper is 21.

No decimal display. 1 to 160.

160

When J2 Jumper is 41.

No decimal display 2 to 320.

320

STOP

Display

When operation sigr^i F (forward) or R (reverse) is rtot input or when

ORiVE-SW on the operation panel is STOP, OFF is displayed.

OFF

When operation signal is complete and SPEED input signal is less than

minimjm frequency or when DRIVE-SW on the operation parel is in

RUN and SPEED input is 0. LS is displayed.

LS

UP wilt lUcker when insufficient input voltage is sensed.

UP

OP wU flicker when over voliage is sensed.

OP

Display

OC will flicker when over current is sensed.

OC

OH will flicker when overtemperature is sensed. (15 HP arM Larger.)

OH

When a protection circuit is activated and there is a flicker display, turn off the

power and eliminate the cause of the fault and restart.

For details, refer 1o section “FAULT DETECTION AND REPAIR.“