Note: If acce eration/deceleration is performed with a short preset rate and high
inertia, OC (over current), or over voltage/potential (OP) protection circuit
may be activated. If the fault signal relay is activated, check the cause
and take necessary action such as increasing the accel/decel rates.
d) Motor coast stop and controlled stop
Coast stop or controlled stop is determined by the input signal to ST or STI
terminal. Opening MC AUX. gives coast stop, otherwise unit will go through
controlled (programmed) stop.
DRIVE
switch
orR
MC
^ ST (STI)
COM
MC
DRIVE
switch
Spssd
Hh
>
Hh
y
/
Conirotsd
stop
Cosst
stop
4.
Switching between commercial power source and inverter output. (Bypass)
Power
MC2 must be provided in order
to protect the transistors in the
Inverter unit from damage.
MC2 and MC3 must be equipped
with mechanical interlock (reversing
contactors).
Protection circuit may be activated when
switching from commercial power to
inverter while the motor is spinning.
MCI
MC2
MC3
Switching sequence
5.
Parallel motor operation
• The total current of the motors must not
exceed the rated current of the inverter.
• Add a thermal relay for each motor for
overload protection.
29