beautypg.com

Neptronic – AERCO CXT-E Retrofit Kit User Manual

Page 39

background image

ECS and CXT-E Retrofit Instructions Kit # 27004-TAB

Technical Instruction Document

TID-0141_0A

12/30/2014

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288 Page 39 of 76

2. Slide the Actuator onto the Linkage Assembly Shaft (Figures 4-2 & 4-4). Ensure that the pin

on the Linkage Assembly is inserted in the center slot on the bottom of the Actuator (Figure
4-4).

3. Press down on the Linkage Adapter and verify that the Indicator Plate is aligned with the “0”

Scale marking.

4. With the Indicator Plate properly aligned, tighten the U-bolt hex nuts using an 8 mm wrench.

Torque the nuts to 60 in-lbs.

5. This completes the mechanical installation of the Actuator Assembly. The electrical

connections will be made during installation of the Control Box in section 4.7.


0

90

neptronic

1 2 3

COVER
SET SCREW

CLUTCH

DIAL &

POINTER

CENTER

SLOT

COVER

CABLE

CONNECTOR

LINKAGE

SHAFT

Figure 4-4. Actuator Assembly, Part No. 69170