MORNING WARM-UP (VAV only with PC Accessed/CCN

Operation) — Morning warm-up occurs when the control has

been programmed to turn on heat prior to the Occupied mode

to be ready for occupancy mode. Morning warm-up is a condi-

tion in VAV systems that occurs when the Temperature Com-

pensated Start algorithm calculates a biased occupied start time

and the unit has a demand for heating. The warm-up will con-

tinue into the occupied period as long as there is a need for

heat. During warm-up, the unit can continue heating into the

occupied period, even if occupied heating is disabled. When

the heating demand is satisfied, the warm-up condition will ter-

minate. To increase or decrease the heating demand, use

Service Tool software to change the Occupied Heating set

point.

NOTE: To utilize Morning Warm-Up mode, the unit occu-

pancy schedule must be accessed via Service Tool, Building

Supervisor, or ComfortWORKS® software or accessory

Remote Enhanced Display. The PC can access the base control

board via the 3-wire communication bus or via an RJ-11 con-

nection to the CCN terminal on the base control board. See

Fig. 27.

For current software (version 3.0 or later), the Low Tem-

perature Minimum Damper Position Override (LOWMDP)

has a 0 to 100% limit, with a default of 100%. Think of the

LOWMDP as a second minimum damper position. This

LOWMDP limit change requires access to the unit software

with a computer equipped with Building Supervisor, Ser-

vice Tool, or ComfortWORKS Software.

When the LOWMDP is in effect the outdoor dampers will

remain at the LOWMDP position (typically set to 0% closed)

during heating, even in the Occupied period. For the LOW-

MDP to be in effect the LOWMDP must be less than the mini-

mum damper position (MDP) and the RAT (return-air tempera-

ture) must be less than the OHSP (occupied heat set point)

minus 2.5° F. Table 40 summarizes the operational require-

ments and controlling factors for occupied heat and morning

warm-up.
MORNING WARM-UP (VAV Only with Stand-Alone

Operation) — When the unit operates in stand-alone mode,

morning warm-up occurs when the unit is energized in Occu-

pied mode and return-air temperature (RAT) is below 68 F.

Warm-up will not terminate until the RAT reaches 68 F. The

heat interlock relay output is energized during morning warm-

up. (A field-installed 24-vdc heat interlock relay is required.)

The output will be energized until the morning warm-up cycle

is complete. Refer to Fig. 59 for heat interlock relay wiring.

Table 39 — Navigator Display Menu Structure

RUN

STATUS

SERVICE

TEST

TEMPERATURES PRESSURES

SET

POINTS

INPUTS

OUTPUTS CONFIGURATION TIME CLOCK

OPERATING

MODES

ALARMS

Auto Display

(VIEW)

SERVICE

TEST

SUPPLY AIR

TEMPERATURE

N/A

SETPOINT

SELECT

COOL

INPUT#1

HEAT

OUTPUT

1

Display

Configuration

(DISP)

Time

(TIME)

N/A

Currently

Active

Alarms

(CRNT)

Software

Version
(VERS)

HEAT

OUTPUT#1

SUPPLY AIR

TEMPERATURE 1

N/A

COOLING

SETPOINT

1

COOL

INPUT#2

HEAT

OUTPUT

2

CCN

Configuration

(CCN)

Date

(DATE)

N/A

Reset all

Current

Alarms

(RCRN)

HEAT

OUTPUT#2

SUPPLY AIR

TEMPERATURE 2

N/A

COOLING

SETPOINT

2

HEAT

INPUT#1

HEAT

OUTPUT

3

Stage Gas

Configuration

(CNFG)

Occupancy

and

Unoccupancy

Schedule

Number
(SCHD)

Alarm

History

(HIST)

HEAT

OUTPUT#3

SUPPLY AIR

TEMPERATURE 3

HEATING

SETPOINT

1

HEAT

INPUT#1

HEAT

OUTPUT

4

Reset
Alarm

History

(RHIS)

HEAT

OUTPUT#4

HEATING

SETPOINT

2

SUPPLY

FAN

STATUS

HEAT

OUTPUT

5

HEAT

OUTPUT#5

HEAT

OUTPUT

6

HEAT

OUTPUT#6

Run Status

Service

Test

Temperature

s

Pressures

Setpoints

Inputs

Outputs

Configu

ration

Time C

lock

Opera

ting M

odes

Alarm

s

E NTE

R

E S C

M O D

E

Alarm Status

N A V

I G A

T O R

C o m f o

r t

L i n k

Fig. 60 — Navigator Display

This manual is related to the following products: