beautypg.com

Carrier 48AJ User Manual

Page 60

background image

60

8. Press “READ/WRITE” key, to enter the new value. The

desired set point value will alternately flash to indicate

that the new value has been stored.

9. Fire-speed override mode is available by contact closure

between terminals S1 and CC.

10. If the VFD is to be controlled by an external control sys-

tem, other than the factory-supplied duct static pressure

transducer, follow these steps:

a. Install a jumper between S2 and CC. This jumper

will disable the PID (Proportional Integral Deriva-

tive) control loop in the VFD. The VFD is set to

follow an external speed reference signal from the

control system.

b. Connect the field-supplied speed reference (4-20

mA) signal across terminals IV and P24.

11. Once all the changes have been made, open the IFCB.

12. Wait for the VFD display to go blank and remove VFD

cover without touching any interior components. Make

sure that the charge indicator lamp is out. If still lit, wait

until lamp goes completely out. This may take several

minutes.

13. Replace jumper across terminals ST and CC.
14. Replace VFD cover.
15. Close the IFCB. The VFD is now powered and the fan

will operate.

Table 12 — Carrier Default Program Parameter Values

*These settings differ from the Toshiba defaults and are required for Carrier applications.

IMPORTANT: The Carrier factory default values for the

VFD may be different than the default values of the manu-

facturer. Refer to the Carrier literature when checking

default values. The following default values have been

changed from the manufacturer settings to closely match

the VFD operation with a Carrier VAV unit. Refer to

Tables 12 and 13.

PARAMETER GROUP

PARAMETER

DEFAULT VALUE

SetP

(Setup)

ACC1

60.0 Sec

DEC1

60.0 Sec

UL

60.0 Hz

LL

10.0 Hz*

Luln

1

P3

20%

F-P3

0.0 Hz

P4

100%

F-P4

60 Hz

tHr1

See Table 13

StC1

0

StL1

110%

OLN

1

tYP

5*

Gr.F

(Fundamental)

FH

60 Hz

Pt

2

Gr.Fb

(Feedback)

FbP1

1*

Fbln

2

GP

.30

Gl

2 sec

GA

0

GFS

80

P1LL

10

PuL

1

PuUl

10

PuLL

10

Gr.SF

(Frequency Settings)

Fsor

60 Hz

Gr.Pn

(Panel Control)

Fr

0*

Gr.St

(Terminal Selection)

1t

1

1t0

0

1t1

56

1t2

13

1t3

3

1t4

10

Gr.Pr

(Protection)

UuC

1*

UuCt

2

ArSt

3

Gr.Ut

(Utility)

Cnod

1*

Fnod

2*

bLPn

1*

This manual is related to the following products: