beautypg.com

Carrier 48AJ User Manual

Page 61

background image

61

Table 13 — Motor Electronic Thermal Protection (tHr) for Toshiba TOSVERT 130-E3 VFD

*IFM Letter refers to the 15th digit (Motor Option) of the unit model number

TOSHIBA TOSVERT VF-S9 VFD — The VFD must be

powered up, however, since it is located near the indoor fan,

operation of the fan is not desirable. To disable the fan and set

the duct static pressure, perform the following procedure:

1. Open the Indoor Fan Circuit Breaker (IFCB). This will

shut off power to the VFD.

2. Wait for the VFD display to go blank and the charge

lamplight to go out. Remove the VFD cover without

touching any interior components. It may take several

minutes for the VFD to fully discharge.

3. Remove jumper between R and CC on the terminal block

and replace the VFD cover. This will disable the running

of the VFD. Refer to Fig. 58.

4. Close the IFCB and energize the Indoor Fan Contactor

(IFC). The VFD is now powered but the fan will not

operate.

5. On the front of the VFD is a keypad, which is used to

change the VFD set point. At this point the drive should

be disabled and the display read “OFF”. If the current

output frequency is displayed then verify that the R and

CC jumpers have been removed.

6. Press either the “DOWN ARROW” or “UP ARROW”

key once, this will display the current frequency set point.

7. Press either the “DOWN ARROW” or “UP ARROW”

key to change set point to the appropriate duct static set

point desired. This number may be adjusted based on the

amount of static pressure (in. wg) required. Refer to the

Table 8 to identify the VFD Set Point.

8. Press “ENT” key, to enter the new value. The desired set

point value will alternately flash to indicate that the new

value has been stored.

9. Fire-speed override mode is available by contact closure

between terminals S1 and CC.

10. If the VFD is to be controlled by an external control sys-

tem, other than the factory-supplied duct static pressure

transducer, follow these steps:

a. Install a jumper between S2 and CC. This jumper

will disable the PID (Proportional Integral Deriva-

tive) control loop in the VFD. The VFD is set to

follow an external speed reference signal from the

control system.

b. Connect the field-supplied speed reference

(4-20 mA) signal across terminals II and P24. See

Fig. 58.

11. Once all the changes have been made, open the IFCB.

12. Wait for the VFD display to go blank and the charge

lamplight to go out. Remove the VFD cover without

touching any interior components. It may take several

minutes for the VFD to fully discharge.

13. Replace jumper across terminals R and CC.
14. Replace VFD cover.
15. Close the IFCB. The VFD is now powered and the fan

will operate.

MOTOR

STANDARD EFFICIENCY

HIGH EFFICIENCY

Hp

kW

IFM

Letter*

230 V

Setting

380V

Setting

460V

Setting

575V

Setting

IFM

Letter*

230V

Setting

460V

Setting

5

3.73

A

66

100

72

89

L

72

72

7.5

5.60

B

100

100

80

76

M

100

80

10

7.46

C

96

94

97

91

N

96

100

15

11.19

D

78

94

100

100

P

78

100

20

14.92

E

87

94

100

95

Q

82

100

25

18.65

F

86

84

94

100

R

86

91

30

22.38

G

99

92

100

S

86

80

40

29.84

H

89

85

85

T

89

85

A high voltage potential can exist with the indoor fan cir-

cuit breaker open. The charge lamp LED, located on the

upper left corner of the Toshiba TOSVERT VF-S9 VFD

front cover, will indicate charged capacitors. DO NOT

TOUCH internal high voltage parts if LED is lit.

IMPORTANT: The Carrier factory default values for the

VFD may be different than the default values of the manu-

facturer. Refer to the Carrier literature when checking

default values. The following default values have been

changed from the manufacturer settings to closely match

the VFD operation with a Carrier VAV unit. Refer to

Tables 14 and 15.

This manual is related to the following products: