beautypg.com

Carrier 48AJ User Manual

Page 71

background image

71

Table 25 — Fan Performance, 48AW,AY040,050 — Horizontal Discharge Units

LEGEND
Bhp — Brake Horsepower
NOTES:

1. Fan performance is based on wet coils, economizer, roof curb,

cabinet losses, and clean 2-in. filters.

2. Conversion — Bhp to watts:

3. Variable Air Volume units will operate down to 70 cfm/ton. Per-

formance at 70 cfm/ton is limited to unloaded operation and
may be additionally limited by edb (entering dry bulb) and ewb
(entering wet bulb) conditions.

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

8,000

536

3.18

582

3.58

626

3.99

668

4.41

708

4.83

747

5.27

785

5.71

821

6.16

9,000

588

4.17

630

4.60

670

5.04

709

5.48

746

5.93

782

6.38

818

6.84

852

7.31

10,000

642

5.35

680

5.80

717

6.27

753

6.73

787

7.20

821

7.68

854

8.16

886

8.65

11,000

696

6.72

732

7.20

766

7.69

799

8.18

831

8.67

863

9.17

893

9.68

923

10.18

12,000

751

8.29

784

8.80

816

9.32

847

9.83

877

10.35

906

10.87

935

11.40

964

11.92

13,000

807

10.09

837

10.62

867

11.16

896

11.70

924

12.24

952

12.78

979

13.33

1006

13.88

14,000

863

12.12

891

12.67

919

13.23

946

13.79

973

14.36

999

14.92

1025

15.49

1050

16.06

15,000

919

14.38

946

14.96

972

15.54

997

16.12

1023

16.71

1047

17.30

1072

17.89

1096

18.48

16,000

975

16.90

1000

17.49

1025

18.09

1049

18.70

1073

19.31

1097

19.92

1120

20.53

1143

21.15

17,000

1032

19.67

1056

20.29

1079

20.91

1102

21.54

1125

22.17

1147

22.80

1169

23.44

1191

24.07

18,000

1089

22.71

1111

23.35

1134

23.99

1155

24.64

1177

25.29

1198

25.95

1219

26.60

1240

27.26

19,000

1146

26.04

1167

26.69

1188

27.35

1209

28.02

1230

28.69

1250

29.37

1270

30.04

1290

30.72

20,000

1203

29.65

1224

30.32

1244

31.00

1263

31.69

1283

32.38

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.8

2.0

2.2

2.4

2.6

2.8

3.0

3.2

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

8,000

857

6.63

891

7.09

923

7.57

955

8.05

986

8.54

1016

9.03

1045

9.53

1073

10.03

9,000

885

7.79

918

8.28

949

8.77

980

9.27

1010

9.77

1039

10.28

1067

10.80

1095

11.32

10,000

917

9.14

948

9.65

978

10.15

1008

10.67

1036

11.19

1064

11.72

1092

12.25

1119

12.79

11,000

953

10.70

982

11.21

1010

11.74

1038

12.27

1066

12.81

1093

13.35

1119

13.90

1145

14.45

12,000

991

12.46

1019

12.99

1046

13.53

1072

14.08

1098

14.63

1124

15.19

1149

15.76

1174

16.32

13,000

1032

14.43

1058

14.99

1084

15.55

1109

16.11

1134

16.68

1158

17.26

1182

17.84

1206

18.42

14,000

1075

16.64

1100

17.21

1124

17.79

1148

18.38

1171

18.97

1195

19.55

1218

20.15

1241

20.75

15,000

1120

19.08

1143

19.68

1166

20.27

1189

20.88

1211

21.49

1234

22.09

1256

22.71

1277

23.32

16,000

1165

21.76

1188

22.38

1210

23.00

1231

23.62

1253

24.25

1274

24.88

1295

25.51

17,000

1213

24.71

1234

25.35

1255

25.99

1276

26.63

1296

27.27

18,000

1261

27.92

1281

28.58

19,000

20,000

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

3.4

3.6

3.8

4.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

8,000

1100

10.54

1126

11.05

1152

11.56

1177

12.08

9,000

1122

11.85

1148

12.38

1174

12.91

1199

13.45

10,000

1145

13.33

1171

13.88

1196

14.43

1221

14.99

11,000

1171

15.01

1196

15.57

1220

16.14

1245

16.72

12,000

1199

16.90

1223

17.48

1247

18.06

1270

18.65

13,000

1230

19.01

1253

19.60

1276

20.20

1299

20.80

14,000

1263

21.35

1285

21.96

15,000

1299

23.94

16,000

17,000

18,000

19,000

20,000

Watts =

Bhp x 746

Motor Efficiency

This manual is related to the following products: